East Energy Electrical Engineering presents the 0.6/1kV Aerial Bundled Cable (ABC), a high-performance overhead power distribution solution engineered exclusively to meet AS/NZS 3560.1 standards—the benchmark for reliability in Australian and New Zealand climates. This cable integrates advanced manufacturing 工艺 (craftsmanship) with premium materials to deliver exceptional durability, making it ideal for both rural and urban power networks facing harsh environmental conditions.
At its core, the cable features aluminum alloy (AAAC) or aluminum (AAC) conductors wrapped in UV-resistant cross-linked polyethylene (XLPE) insulation, paired with a black high-density polyethylene (HDPE) jacket for maximum protection. The innovative design includes an optional integrated neutral messenger wire, simplifying installation while ensuring compliance with strict grounding requirements. With a temperature range of -40°C to +90°C and flame-retardant properties (per IEC 60332-1), this ABC cable excels in extreme heat, cold, and high-humidity environments—from coastal regions to alpine areas.

| Parameter | Specification |
|---|---|
| Standard | AS/NZS 3560.1, IEC 60502-1 |
| Rated Voltage | 0.6/1kV |
| Conductor Material | Aluminum Alloy (AAAC) / Aluminum (AAC) |
| Insulation Material | UV-resistant Cross-linked Polyethylene (XLPE) |
| Jacket Material | Black HDPE (High-Density Polyethylene) |
| Core Configuration | 3/4/5 Cores + Integrated Neutral Messenger Wire (Optional) |
| Temperature Range | -40°C to +90°C |
| Minimum Bending Radius | 10 × Cable Diameter |
| Tensile Strength | ≥120 MPa (AAAC) / ≥60 MPa (AAC) |
| Fire Performance | Flame-retardant (IEC 60332-1) |
Available Sizes
| Model | Conductor Size (mm²) | Insulation Thickness (mm) | Overall Diameter (mm) | Approx. Weight (kg/km) |
|---|---|---|---|---|
| ABC-3×16+NM16 | 16 | 1.4 | 22.5 | 320 |
| ABC-4×25+NM25 | 25 | 1.6 | 28.0 | 480 |
| ABC-5×50+NM50 | 50 | 2.0 | 35.5 | 820 |
0.6/1kV Aerial Bunched Cable(ABC)(Australia/New Zealand Standard)
Nominal area | Number/Dia. | Insulation thickness |
mm² | mm | mm |
2/4*16 | 7/1.72 | 1.3 |
2/3/4*25 | 7/2.20 | 1.3 |
2/3/4*35 | 7/2.58 | 1.3 |
2/3/4*50 | 7/3.00 | 1.5 |
4*70 | 19/2.1 | 4.5 |
1/4*95 | 19/2.58 | 1.7 |
4*120 | 19/2.9 | 1.7 |
The UV-stabilized XLPE insulation and anti-oxidation conductor coating prevent degradation from prolonged sun exposure, salt spray, and humidity—extending the cable’s service life to over 30 years in coastal, desert, and alpine regions. This durability directly reduces long-term maintenance costs for power utilities.
Compliance with AS/NZS 3560.1 and IEC 60502-1 standards ensures the cable meets global safety benchmarks. The integrated neutral messenger wire eliminates the need for separate grounding components, reducing installation complexity and minimizing safety risks during setup.
Pre-assembled cable bundles cut on-site labor time by 40% compared to traditional overhead wiring. The cable’s flexible design (minimum bending radius of 10× cable diameter) allows for easy routing around obstacles, making it suitable for fast-paced construction projects.
East Energy offers tailored solutions to match specific project needs, including custom core configurations, conductor sizes (16mm² to 120mm²), and insulation thicknesses. Our OEM services enable branding alignment and technical adjustments to meet unique regional or client requirements.
The 0.6/1kV ABC cable is the primary choice for overhead power networks in:
Rural areas: Reliable power delivery to remote communities with limited maintenance access.
Suburban zones: Safe integration with residential and commercial infrastructure.
Industrial sites: Heavy-duty performance for factories and manufacturing facilities.
It supports clean energy initiatives by connecting solar farms and wind turbines to the main grid, with weather-resistant properties ensuring consistent performance in outdoor renewable installations.
Ideal for construction sites and emergency response scenarios, the cable’s quick installation and robust design provide temporary, stable power without compromising safety.
Our ABC cables undergo rigorous testing by global authorities SGS and Intertek to verify compliance with AS/NZS 3560.1—guaranteeing reliability and performance. Every batch meets strict quality control standards to avoid defects.
With years of experience supplying to Australian and New Zealand clients, we understand local climate challenges and regulatory requirements. Our team provides tailored technical support to ensure seamless installation and compliance.
We use recyclable materials in cable production, aligning with Australia’s Clean Energy initiatives. This commitment to sustainability reduces environmental impact while maintaining product durability.
Whether you need custom conductor sizes, insulation tweaks, or branded packaging, our OEM team delivers solutions within short lead times. We collaborate closely with clients to turn technical requirements into tangible products.
No. This cable is designed exclusively for overhead use and must not be buried—even in conduits. Burial can damage the insulation and compromise safety, leading to performance issues or failures.
Yes. We offer flexible customization, including 3-core, 4-core, or 5-core setups, plus optional integrated neutral messenger wires. Contact our team to discuss your specific core configuration needs.
The cable operates reliably in ambient temperatures ranging from -40°C to +90°C, with a maximum conductor temperature of 90°C (per IEC standards). This range makes it suitable for Australia’s hot summers and New Zealand’s cold winters.
East Energy Electrical Engineering presents the 0.6/1kV Aerial Bundled Cable (ABC), a high-performance overhead power distribution solution engineered exclusively to meet AS/NZS 3560.1 standards—the benchmark for reliability in Australian and New Zealand climates. This cable integrates advanced manufacturing 工艺 (craftsmanship) with premium materials to deliver exceptional durability, making it ideal for both rural and urban power networks facing harsh environmental conditions.
At its core, the cable features aluminum alloy (AAAC) or aluminum (AAC) conductors wrapped in UV-resistant cross-linked polyethylene (XLPE) insulation, paired with a black high-density polyethylene (HDPE) jacket for maximum protection. The innovative design includes an optional integrated neutral messenger wire, simplifying installation while ensuring compliance with strict grounding requirements. With a temperature range of -40°C to +90°C and flame-retardant properties (per IEC 60332-1), this ABC cable excels in extreme heat, cold, and high-humidity environments—from coastal regions to alpine areas.

| Parameter | Specification |
|---|---|
| Standard | AS/NZS 3560.1, IEC 60502-1 |
| Rated Voltage | 0.6/1kV |
| Conductor Material | Aluminum Alloy (AAAC) / Aluminum (AAC) |
| Insulation Material | UV-resistant Cross-linked Polyethylene (XLPE) |
| Jacket Material | Black HDPE (High-Density Polyethylene) |
| Core Configuration | 3/4/5 Cores + Integrated Neutral Messenger Wire (Optional) |
| Temperature Range | -40°C to +90°C |
| Minimum Bending Radius | 10 × Cable Diameter |
| Tensile Strength | ≥120 MPa (AAAC) / ≥60 MPa (AAC) |
| Fire Performance | Flame-retardant (IEC 60332-1) |
Available Sizes
| Model | Conductor Size (mm²) | Insulation Thickness (mm) | Overall Diameter (mm) | Approx. Weight (kg/km) |
|---|---|---|---|---|
| ABC-3×16+NM16 | 16 | 1.4 | 22.5 | 320 |
| ABC-4×25+NM25 | 25 | 1.6 | 28.0 | 480 |
| ABC-5×50+NM50 | 50 | 2.0 | 35.5 | 820 |
0.6/1kV Aerial Bunched Cable(ABC)(Australia/New Zealand Standard)
Nominal area | Number/Dia. | Insulation thickness |
mm² | mm | mm |
2/4*16 | 7/1.72 | 1.3 |
2/3/4*25 | 7/2.20 | 1.3 |
2/3/4*35 | 7/2.58 | 1.3 |
2/3/4*50 | 7/3.00 | 1.5 |
4*70 | 19/2.1 | 4.5 |
1/4*95 | 19/2.58 | 1.7 |
4*120 | 19/2.9 | 1.7 |
The UV-stabilized XLPE insulation and anti-oxidation conductor coating prevent degradation from prolonged sun exposure, salt spray, and humidity—extending the cable’s service life to over 30 years in coastal, desert, and alpine regions. This durability directly reduces long-term maintenance costs for power utilities.
Compliance with AS/NZS 3560.1 and IEC 60502-1 standards ensures the cable meets global safety benchmarks. The integrated neutral messenger wire eliminates the need for separate grounding components, reducing installation complexity and minimizing safety risks during setup.
Pre-assembled cable bundles cut on-site labor time by 40% compared to traditional overhead wiring. The cable’s flexible design (minimum bending radius of 10× cable diameter) allows for easy routing around obstacles, making it suitable for fast-paced construction projects.
East Energy offers tailored solutions to match specific project needs, including custom core configurations, conductor sizes (16mm² to 120mm²), and insulation thicknesses. Our OEM services enable branding alignment and technical adjustments to meet unique regional or client requirements.
The 0.6/1kV ABC cable is the primary choice for overhead power networks in:
Rural areas: Reliable power delivery to remote communities with limited maintenance access.
Suburban zones: Safe integration with residential and commercial infrastructure.
Industrial sites: Heavy-duty performance for factories and manufacturing facilities.
It supports clean energy initiatives by connecting solar farms and wind turbines to the main grid, with weather-resistant properties ensuring consistent performance in outdoor renewable installations.
Ideal for construction sites and emergency response scenarios, the cable’s quick installation and robust design provide temporary, stable power without compromising safety.
Our ABC cables undergo rigorous testing by global authorities SGS and Intertek to verify compliance with AS/NZS 3560.1—guaranteeing reliability and performance. Every batch meets strict quality control standards to avoid defects.
With years of experience supplying to Australian and New Zealand clients, we understand local climate challenges and regulatory requirements. Our team provides tailored technical support to ensure seamless installation and compliance.
We use recyclable materials in cable production, aligning with Australia’s Clean Energy initiatives. This commitment to sustainability reduces environmental impact while maintaining product durability.
Whether you need custom conductor sizes, insulation tweaks, or branded packaging, our OEM team delivers solutions within short lead times. We collaborate closely with clients to turn technical requirements into tangible products.
No. This cable is designed exclusively for overhead use and must not be buried—even in conduits. Burial can damage the insulation and compromise safety, leading to performance issues or failures.
Yes. We offer flexible customization, including 3-core, 4-core, or 5-core setups, plus optional integrated neutral messenger wires. Contact our team to discuss your specific core configuration needs.
The cable operates reliably in ambient temperatures ranging from -40°C to +90°C, with a maximum conductor temperature of 90°C (per IEC standards). This range makes it suitable for Australia’s hot summers and New Zealand’s cold winters.
Code: ABC 0.6/1kV.
Standards:HD 626 S1:1996 Part5-Section D,AMKA(SFS 2200).
Construction: Phase Conductors:Aluminum conductors with XLPE insulation.
Neutral Messenger:Aluminum conductors.
Application: Aerial Bundled Conductors are used for tributary networks of power buildings and their internal networks.
Installation: These cables are not allowed to be buried, even in conduits.
Dimensions of Phase Conductors
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameter | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | tolerance | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
16 | 4.4 | ±0.05 | 1.4 | 7.1 | 7.3 | 70 | ||
25 | 5.9 | ±0.02 | 1.4 | 8.3 | 9.1 | 95 | ||
35 | 6.9 | ±0.02 | 1.6 | 9.7 | 10.5 | 115 | ||
50 | 8.1 | ±0.25 | 1.6 | 10.8 | 11.8 | 140 | ||
70 | 9.7 | ±0.25 | 1.8 | 12.8 | 13.8 | 180 | ||
120 | 12.8 | ±0.30 | 2.0 | 16.2 | 17.4 | 250 | ||
* Defined for ambient temperature of 25℃ and max.conductor temperature of 70℃.
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameter | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | tolerance | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
25 | 5.9 | ±0.02 | 5.5 | 6.3 | 7.4 | |||
35 | 6.9 | ±0.02 | 6.5 | 7.3 | 10.3 | |||
50 | 8.1 | ±0.25 | 7.6 | 8.6 | 14.2 | |||
70 | 9.7 | ±0.25 | 9.2 | 10.2 | 20.6 | |||
95 | 11.4 | ±0.30 | 10.8 | 12.0 | 27.9 | |||
Dimensions of Cable Bundle
Number of Phase Cores× Cross Section +Public Lighting Conductors + Neutral Cross Section (mm²) | Bundle Diameter Approx. (mm) |
1×16+25 | 15 |
3×16+25 | 22 |
4×16+25 | 22 |
3×25+35 | 26 |
4×25+35 | 26 |
3×35+50 | 30 |
3×50+70 | 35 |
3×70+95 | 41 |
3×120+95 | 47 |
LV-ABC Lines with Insulated Neutral Messenger
Code: ABC 0.6/1kV.
Standards:HD 626 S1:1996 Part 6-Section E,AMKA(SFS 2200)
Construction: Aluminum conductors with XLPE insulation.
Application:Aerial Bundled Conductors are used for tributary networks of power buildings and their internal networks.
Installation:These cables are not allowed to be buried,even in conduits.
Dimensions of Phase Conductors
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameten | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | max. | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
16 | 4.6 | 5.1 | 1.2 | 7.0 | 7.8 | |||
25 | 5.8 | 6.3 | 1.4 | 8.6 | 9.4 | 112 | ||
35 | 6.8 | 7.3 | 1.6 | 10.0 | 10.9 | 138 | ||
50 | 7.9 | 8.4 | 1.6 | 11.1 | 12.0 | 168 | ||
70 | 9.7 | 10.2 | 1.8 | 13.3 | 14.2 | 213 | ||
95 | 11.0 | 12.0 | 1.8 | 14.6 | 15.7 | 258 | ||
120 | 12.0 | 13.1 | 1.8 | 15.6 | 16.7 | 306 | ||
150 | 13.9 | 15.0 | 1.7 | 17.3 | 18.6 | 344 | ||
* Defined for ambient temperature of 30℃ and max. conductor temperature of 90℃.
Dimensions of Neutral Messenger Conductors
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameter | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | tolerance | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
54.6 | 9.2 | 9.6 | 1.6 | 12.3 | 13.0 | 16.6 | ||
70 | 10.0 | 10.2 | 1.5 | 12.9 | 13.6 | 20.5 | ||
95 | 12.2 | 12.9 | 1.6 | 15.3 | 16.3 | 27.5 | ||
* Defined for ambient temperature of 30℃ and max.conductor temperature of 90℃.
Dimensions of Cable Bundle
Number of Phase Cores× Cross Section +Public Lighting Conductors +Neutral Cross Section (mm²) | Bundle Diameter Approx. (mm) |
3×25+54.6 | 30.0 |
3×35+K×16+54.6 | 33.0 |
3×50+K×16+54.6 | 36.0 |
3×70+K×16+54.6 | 37.5 |
3×70+K×25+54.6 | 40.0 |
3×70+K×16+70 | 41.0 |
3×95+K×16+70 | 44.0 |
3×120+K×16+70 | 46.0 |
3×120+K×16+95 | 47.0 |
3×150+K×16+70 | 48.0 |
3×150+K×16+95 | 49.0 |
* Note: K number of public lighting conductors(K can be equal to 0.1.2.or 3).
Code: ABC 0.6/1kV.
Standards:HD 626 S1:1996 Part5-Section D,AMKA(SFS 2200).
Construction: Phase Conductors:Aluminum conductors with XLPE insulation.
Neutral Messenger:Aluminum conductors.
Application: Aerial Bundled Conductors are used for tributary networks of power buildings and their internal networks.
Installation: These cables are not allowed to be buried, even in conduits.
Dimensions of Phase Conductors
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameter | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | tolerance | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
16 | 4.4 | ±0.05 | 1.4 | 7.1 | 7.3 | 70 | ||
25 | 5.9 | ±0.02 | 1.4 | 8.3 | 9.1 | 95 | ||
35 | 6.9 | ±0.02 | 1.6 | 9.7 | 10.5 | 115 | ||
50 | 8.1 | ±0.25 | 1.6 | 10.8 | 11.8 | 140 | ||
70 | 9.7 | ±0.25 | 1.8 | 12.8 | 13.8 | 180 | ||
120 | 12.8 | ±0.30 | 2.0 | 16.2 | 17.4 | 250 | ||
* Defined for ambient temperature of 25℃ and max.conductor temperature of 70℃.
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameter | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | tolerance | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
25 | 5.9 | ±0.02 | 5.5 | 6.3 | 7.4 | |||
35 | 6.9 | ±0.02 | 6.5 | 7.3 | 10.3 | |||
50 | 8.1 | ±0.25 | 7.6 | 8.6 | 14.2 | |||
70 | 9.7 | ±0.25 | 9.2 | 10.2 | 20.6 | |||
95 | 11.4 | ±0.30 | 10.8 | 12.0 | 27.9 | |||
Dimensions of Cable Bundle
Number of Phase Cores× Cross Section +Public Lighting Conductors + Neutral Cross Section (mm²) | Bundle Diameter Approx. (mm) |
1×16+25 | 15 |
3×16+25 | 22 |
4×16+25 | 22 |
3×25+35 | 26 |
4×25+35 | 26 |
3×35+50 | 30 |
3×50+70 | 35 |
3×70+95 | 41 |
3×120+95 | 47 |
LV-ABC Lines with Insulated Neutral Messenger
Code: ABC 0.6/1kV.
Standards:HD 626 S1:1996 Part 6-Section E,AMKA(SFS 2200)
Construction: Aluminum conductors with XLPE insulation.
Application:Aerial Bundled Conductors are used for tributary networks of power buildings and their internal networks.
Installation:These cables are not allowed to be buried,even in conduits.
Dimensions of Phase Conductors
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameten | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | max. | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
16 | 4.6 | 5.1 | 1.2 | 7.0 | 7.8 | |||
25 | 5.8 | 6.3 | 1.4 | 8.6 | 9.4 | 112 | ||
35 | 6.8 | 7.3 | 1.6 | 10.0 | 10.9 | 138 | ||
50 | 7.9 | 8.4 | 1.6 | 11.1 | 12.0 | 168 | ||
70 | 9.7 | 10.2 | 1.8 | 13.3 | 14.2 | 213 | ||
95 | 11.0 | 12.0 | 1.8 | 14.6 | 15.7 | 258 | ||
120 | 12.0 | 13.1 | 1.8 | 15.6 | 16.7 | 306 | ||
150 | 13.9 | 15.0 | 1.7 | 17.3 | 18.6 | 344 | ||
* Defined for ambient temperature of 30℃ and max. conductor temperature of 90℃.
Dimensions of Neutral Messenger Conductors
Cross Section | Conductor Diameter | Thickness of Insulation | Core Diameter | Current Carrying Capacity | Breaking Load | |||
(mm²) | min. | tolerance | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | ||||
54.6 | 9.2 | 9.6 | 1.6 | 12.3 | 13.0 | 16.6 | ||
70 | 10.0 | 10.2 | 1.5 | 12.9 | 13.6 | 20.5 | ||
95 | 12.2 | 12.9 | 1.6 | 15.3 | 16.3 | 27.5 | ||
* Defined for ambient temperature of 30℃ and max.conductor temperature of 90℃.
Dimensions of Cable Bundle
Number of Phase Cores× Cross Section +Public Lighting Conductors +Neutral Cross Section (mm²) | Bundle Diameter Approx. (mm) |
3×25+54.6 | 30.0 |
3×35+K×16+54.6 | 33.0 |
3×50+K×16+54.6 | 36.0 |
3×70+K×16+54.6 | 37.5 |
3×70+K×25+54.6 | 40.0 |
3×70+K×16+70 | 41.0 |
3×95+K×16+70 | 44.0 |
3×120+K×16+70 | 46.0 |
3×120+K×16+95 | 47.0 |
3×150+K×16+70 | 48.0 |
3×150+K×16+95 | 49.0 |
* Note: K number of public lighting conductors(K can be equal to 0.1.2.or 3).
Code: ABC 11kV.
Standards:SANS 1713.
Construction:Phase Conductors:Aluminum conductors with XLPE insulation.
Neutral Messenger:A stranded galvanized steel conductor with XLPE insulation.
Application: The Aerial Bundled Conductors shall suitable for continuous
operation outdoors in tropical areas at altitudes of up to 2200m above sea
level, humidity of up to 90%, average ambient temperature of+30℃ with
a minimum of - 1℃ and a maximum of +4℃ in direct sunlight, heavy
saline conditions along the coast and isoceraunic levels of up to 180
thunderstorm days per year.
Installation:These cables are not allowed to be buried,even in conduits.
Phase Conductor Characteristics
1 | Conductor size | mm² | 70 | 95 | 185 |
2 | Diameter over conductor.nominal | mm | 9.3-10.2 | 11.6 | 16.4 |
3 | Thickness of dielectric.nominal | mm | 3.4 | 3.4 | 3.4 |
Minimum at a point | mm | 2.96 | 2.96 | 2.96 | |
4 | Diameter over insulation. nominal | mm | 16.1-17.0 | 21.3 | 25.9 |
5 | Diameter over semi-conducting core screen. nominal | mm | 18.1-19 | 23.3 | 27.9 |
6 | Thickness of copper tape.nominal | mm | 0.15 | 1.15 | 2.15 |
7 | Thickness of sheath.nominal | mm | 1.8 | 1.8 | 1.8 |
Minimum at a point | mm | 1.43 | 1.43 | 1.51 | |
8 | Catenary size | mm² | 50 | 50 | 70 |
9 | Overall diameter of bundle.nominal | mm | 55.7 | 67.8 | 79.2 |
10 | Nominal mass | kg/m | 2.64 | 3.25 | 4.65 |
Supporting Catenary Characteristics
1 | Catenary size | mm² | 50 | 70 |
2 | Number of wires | 7 | 7 | |
3 | Wire size(diameter) | mm | 3.0 | 3.6 |
4 | Minimum tensile strength of each wire | kN | 9.26 | 13.13 |
5 | Elongation at break. minimum | % | 3.5 | 4.0 |
6 | Thickness of protective covering | |||
Nominal | mm | 1.2 | 1.2 | |
Minimum at a point | mm | 0.96 | 1.96 | |
7 | Impusewhsandvoag e1.250s | 21kV/5min | 21kV/5min |
Code: ABC 11kV.
Standards:SANS 1713.
Construction:Phase Conductors:Aluminum conductors with XLPE insulation.
Neutral Messenger:A stranded galvanized steel conductor with XLPE insulation.
Application: The Aerial Bundled Conductors shall suitable for continuous
operation outdoors in tropical areas at altitudes of up to 2200m above sea
level, humidity of up to 90%, average ambient temperature of+30℃ with
a minimum of - 1℃ and a maximum of +4℃ in direct sunlight, heavy
saline conditions along the coast and isoceraunic levels of up to 180
thunderstorm days per year.
Installation:These cables are not allowed to be buried,even in conduits.
Phase Conductor Characteristics
1 | Conductor size | mm² | 70 | 95 | 185 |
2 | Diameter over conductor.nominal | mm | 9.3-10.2 | 11.6 | 16.4 |
3 | Thickness of dielectric.nominal | mm | 3.4 | 3.4 | 3.4 |
Minimum at a point | mm | 2.96 | 2.96 | 2.96 | |
4 | Diameter over insulation. nominal | mm | 16.1-17.0 | 21.3 | 25.9 |
5 | Diameter over semi-conducting core screen. nominal | mm | 18.1-19 | 23.3 | 27.9 |
6 | Thickness of copper tape.nominal | mm | 0.15 | 1.15 | 2.15 |
7 | Thickness of sheath.nominal | mm | 1.8 | 1.8 | 1.8 |
Minimum at a point | mm | 1.43 | 1.43 | 1.51 | |
8 | Catenary size | mm² | 50 | 50 | 70 |
9 | Overall diameter of bundle.nominal | mm | 55.7 | 67.8 | 79.2 |
10 | Nominal mass | kg/m | 2.64 | 3.25 | 4.65 |
Supporting Catenary Characteristics
1 | Catenary size | mm² | 50 | 70 |
2 | Number of wires | 7 | 7 | |
3 | Wire size(diameter) | mm | 3.0 | 3.6 |
4 | Minimum tensile strength of each wire | kN | 9.26 | 13.13 |
5 | Elongation at break. minimum | % | 3.5 | 4.0 |
6 | Thickness of protective covering | |||
Nominal | mm | 1.2 | 1.2 | |
Minimum at a point | mm | 0.96 | 1.96 | |
7 | Impusewhsandvoag e1.250s | 21kV/5min | 21kV/5min |