Confirm the system voltage does not exceed the cable rating:
H07V-K: 450/750V (U₀/U), suitable for most low-voltage control and power circuits.
RV: Typically 450/750V or 300/500V depending on the standard and manufacturer.
For three-phase 400V systems, 450/750V is the standard choice. For lower-voltage control circuits, 300/500V may be sufficient.
Class 5 (fine strand): Highest flexibility, best for mobile applications, tight bends, and vibration-prone equipment.
Class 2 (stranded): Moderate flexibility, suitable for fixed installations with occasional bending.
Solid (Class 1): Not recommended for applications requiring mobility.
For enhanced mobility, select Class 5 conductor according to IEC 60228.
Select the conductor size based on:
Continuous load current
Permissible voltage drop
Ambient temperature and grouping
Short-circuit withstand
Typical range: 0.5 mm² to 240 mm². For control panels, 0.5–6 mm² is common. For power connections, 10–240 mm² may be required.
PVC insulation: Standard, rated 70°C continuous. Suitable for most indoor applications.
Heat-resistant PVC: Available for higher temperatures if required.
Flame-retardant PVC: For installations requiring IEC 60332-1 or project-specific fire performance.
Confirm the maximum conductor temperature and ambient conditions.
Indoor dry locations: Standard PVC is adequate.
Humid or wet areas: Confirm suitability or consider alternative insulation.
High-temperature areas: Verify temperature rating against ambient and equipment heat.
Panel and cabinet wiring: Flexible wire simplifies routing and reduces stress on terminals.
Mobile equipment: Select high strand count and appropriate bending radius.
Fixed installation: Typically 4 × outer diameter.
Flexible/mobile installation: Typically 6 × outer diameter or as specified by the manufacturer.
For repeated flexing, follow the recommended minimum bending radius to avoid conductor fatigue.
Select colors for phase, neutral, and protective earth:
Phase: Black, brown, grey, or other colors.
Neutral: Blue.
Protective earth: Green/yellow.
Other: Red, white, orange, etc., for control or signal wiring.
Confirm color requirements against local wiring codes.
H07V-K: EN 50525-2-31, IEC 60227, VDE 0281.
RV: GB/T 5023, JB/T 8734.
Flame retardance: IEC 60332-1.
RoHS / REACH: Confirm compliance if required for the destination market.
Request test reports or certificates of conformity as needed.
Coils: 100 m, 200 m, or custom.
Drums: For larger cross-sections or long lengths.
Cut lengths: Pre-cut with terminals or ferrules if required.
Confirm packaging to protect insulation during transport and storage.
| Parameter | Unit | Typical Range / Option |
|---|---|---|
| Standard | — | EN 50525-2-31, IEC 60227, GB/T 5023 |
| Type | — | RV / H07V-K, single-core flexible wire |
| Rated Voltage U₀/U | V | 450/750 |
| Conductor | — | Flexible copper, Class 5 per IEC 60228 |
| Insulation | — | PVC |
| Conductor Temperature | °C | 70 (continuous) |
| Ambient Temperature | °C | -15 to +70 (fixed installation) |
| Cross-Section Range | mm² | 0.5 – 240 |
| Outer Diameter | mm | Depends on cross-section |
| Bending Radius (fixed) | — | ≥ 4 × outer diameter |
| Bending Radius (flexible) | — | ≥ 6 × outer diameter |
| Flame Retardance | — | Optional, IEC 60332-1 |
| Color | — | Black, blue, brown, grey, green/yellow, red, white, orange, custom |
| Packaging | — | Coil, drum, cut length |
| Length | m | 100, 200, 500, 1000, custom |
| RoHS / REACH | — | Available on request |
Note: Specifications vary by manufacturer and standard. Confirm actual dimensions, temperature rating, and approvals before ordering.
Switchgear and control panel internal wiring
Distribution boards and meter boxes
Electrical equipment and appliance connections
Portable tools and temporary power leads
Lighting circuits and signal wiring
Automation and instrumentation panels
Maintenance and repair wiring where flexibility is required
H07V-K
450/750V
Code:RV,H07V-K,NYAF
Standard:TEC227.VDE0281,BS6004
Construcion:1-Flexible Copper Conductor
2-PVC Insulation
Application :For protected installation in equipment and lighting fitting.
Also for installation in conduit,on and under plaster
Technical Data:Max.operating temperature 70℃
Short ciruit temperature 160℃
Nominal Cross Section | Number and Dia.of wires | Thickness of insulation | Mean overall diameter | Conductor DC resistance at 20℃ | Approx. Total Weight | Max. Curent Carrying Capacity at 30℃ | ||
mm² | No. ×mm | mm | min | max | Q/km | Kg/km | Pipe A | Air A |
1.5 | 27×0.25 | 0.7 | 2.8 | 3.4 | 13.3 | 21.0 | 15 | 24 |
2.5 | 45×0.25 | 0.8 | 3.4 | 4.1 | 7.98 | 32.0 | 20 | 32 |
4 | 50×0.30 | 0.8 | 3.9 | 4.8 | 4.95 | 48.0 | 25 | 42 |
6 | 75×0.30 | 0.8 | 4.4 | 5.3 | 3.30 | 68.0 | 33 | 54 |
10 | 73×0.40 | 1.0 | 5.7 | 6.8 | 1.91 | 113 | 45 | 73 |
16 | 119×0.40 | 1.0 | 6.7 | 8.1 | 1.21 | 174 | 61 | 98 |
25 | 182×0.40 | 1.2 | 8.4 | 10.2 | 0.780 | 282 | 83 | 129 |
35 | 252×0.40 | 1.2 | 9.7 | 11.7 | 0.554 | 378 | 103 | 158 |
50 | 364×0.40 | 1.4 | 11.5 | 13.9 | 0.386 | 543 | 120 | 198 |