| Parameter | Value |
|---|---|
| Code | H07V-R, NYA |
| Rated voltage | 450/750V |
| Standards | IEC 60227, BS 6004, VDE 0281 |
| Conductor | Stranded copper (Class 2) |
| Insulation | PVC |
Conductor: Stranded copper – flexible, high conductivity
Insulation: PVC – moisture, chemical, and temperature resistant
Preferably for:
Indoor installations
Cable ducts
Industrial plants / switching stations
Underground installation (with additional protection)
| Parameter | Value |
|---|---|
| Max. operating temperature | 70°C |
| Short circuit temperature | 160°C |
| mm² | No. × mm | Insulation (mm) | Overall Dia. (mm) | DC Res. @20°C (Ω/km) | Weight (kg/km) | Current Capacity (Pipe A) | Current Capacity (Air A) |
|---|---|---|---|---|---|---|---|
| 1.5 | 7×0.51 | 0.7 | 2.7–3.3 | 12.1 | 22.0 | 16 | 25 |
| 2.5 | 7×0.66 | 0.8 | 3.3–4.0 | 7.41 | 36.0 | 20 | 34 |
| 4 | 7×0.83 | 0.8 | 3.8–4.6 | 4.61 | 52.0 | 26 | 45 |
| 6 | 7×1.02 | 0.8 | 4.3–5.2 | 3.08 | 74.0 | 35 | 57 |
| 10 | 7×1.32 | 1.0 | 5.6–6.7 | 1.83 | 110 | 46 | 75 |
| 16 | 7×1.68 | 1.0 | 6.4–7.8 | 1.15 | 170 | 62 | 100 |
| 25 | 7×2.20 | 1.2 | 8.1–9.7 | 0.727 | 265 | 82 | 130 |
| 35 | 7×2.55 | 1.2 | 9.0–10.9 | 0.524 | 360 | 100 | 160 |
| 50 | 7×3.00 | 1.4 | 10.6–12.8 | 0.387 | 501 | 120 | 200 |
| Feature | Benefit |
|---|---|
| Stranded copper conductor | Flexible, easy to install |
| PVC insulation | Moisture, chemical, and temperature resistant |
| 450/750V rating | Suitable for power and control circuits |
| IEC / BS / VDE compliant | Internationally accepted |
| 70°C max operating temp | Reliable for continuous operation |