Select the cable according to the system voltage and grounding method. U₀ is the rated power-frequency voltage between conductor and screen; U is the rated voltage between conductors. The maximum system voltage Um must not exceed the cable’s specified value.
| System Nominal Voltage | Cable Rated Voltage U₀/U | Maximum System Voltage Um |
|---|---|---|
| 6 kV | 3.6/6 kV | 7.2 kV |
| 10 kV | 6/10 kV | 12 kV |
| 15 kV | 8.7/15 kV | 17.5 kV |
| 20 kV | 12/20 kV | 24 kV |
| 30 kV | 18/30 kV | 36 kV |
| 35 kV | 26/35 kV | 42 kV |
For ungrounded or resonant-grounded systems, select a higher U₀ rating. For effectively grounded systems, the standard U₀/U rating is usually sufficient.
Copper: Higher conductivity, better short-circuit performance, suitable for critical circuits and limited installation space.
Aluminium: Lower weight and cost, suitable for long routes where weight and budget are priorities.
Cross-section: Determine by load current, short-circuit current, voltage drop, ambient temperature, soil thermal resistivity, and grouping factor. Typical medium voltage range: 25–630 mm².
Single-core: Used in three-phase systems with separate cables per phase, often in ducts or trays.
Three-core: Used for direct distribution and fixed installations where one cable carries all three phases. Common for 3.6/6kV to 26/35kV.
Multi-core: Available for specific control or auxiliary applications.
XLPE insulation allows a continuous conductor temperature of 90°C and a short-circuit temperature of 250°C for up to 5 seconds. Insulation thickness is specified by IEC 60502-2 according to voltage rating.
PVC sheathing: General purpose, flame-retardant, cost-effective. Suitable for indoor, duct, and trench installations.
PE sheathing: Better moisture resistance, preferred for direct burial and wet locations.
LSZH sheathing: Low smoke and halogen-free, for tunnels, indoor substations, and public infrastructure.
This product uses PVC sheathing. Confirm whether PVC is acceptable for the project fire and environmental requirements.
Indoor: Cable trays, ducts, switchgear rooms, and substations.
Trenches and cable ducts: PVC sheath provides protection during pulling and against subsequent damage.
Direct burial: Not recommended without additional mechanical protection. Use armoured cable or conduit.
Vertical shafts: Confirm pulling tension and support spacing.
Tunnels and public areas: Check fire performance requirements; LSZH may be required.
Minimum bending radius is typically 12–15 times the cable outer diameter for static installation and 20 times during pulling. Select drum length according to route length, number of joints, transport limits, and installation method.
Specify the applicable standard: IEC 60502-2, GB/T 12706.2, BS 6622, VDE 0276-620, or project-specific requirements.
| Parameter | Unit | Typical Range / Option |
|---|---|---|
| Standard | — | IEC 60502-2, GB/T 12706.2 |
| Rated Voltage U₀/U | kV | 3.6/6, 6/10, 8.7/15, 12/20, 18/30, 26/35 |
| Maximum System Voltage Um | kV | 7.2, 12, 17.5, 24, 36, 42 |
| Number of Cores | — | 1, 3 |
| Conductor | — | Copper or aluminium, Class 1 or 2, 25–630 mm² |
| Insulation | — | XLPE (cross-linked polyethylene) |
| Insulation Temperature | °C | 90 continuous; 250 short-circuit (max. 5 s) |
| Sheathing | — | PVC |
| Operating Temperature | °C | -40 to +90 conductor |
| Bending Radius | — | ≥12 × outer diameter (static); ≥20 × outer diameter (installation) |
| Installation | — | Indoor, cable duct, trench, switchgear, tray |
| Packing | — | Steel or wooden drum; custom drum length available |
Note: Specifications vary by voltage rating and conductor size. Confirm actual dimensions and test data before ordering.
Medium voltage distribution networks in buildings and industrial plants
Indoor switchgear and transformer connections
Cable ducts, trenches, and trays
Substation auxiliary power circuits
Tunnel and infrastructure lighting and power supply
Renewable energy collection systems where PVC sheathing is acceptable

The XLPE Insulated Power Cable is widely used in:
Power transmission and distribution systems
Underground cabling for urban infrastructure
Industrial plants and commercial buildings
Renewable energy systems (solar, wind, etc.)
High Durability: XLPE insulation provides exceptional mechanical strength, heat resistance, and long-term performance in harsh environments.
Energy Efficiency: Designed to minimize energy losses, optimizing power distribution and reducing operational costs.
Environmental Resistance: PVC sheath offers excellent protection against moisture, UV rays, chemicals, and mechanical wear.
Safety: Conforms to the highest international safety and performance standards.
Single-core,CU/XLPE/ATA/PVC or AL/XLPE/ATA/PVC (Table 17)
Conductor Nominal Area | Inulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.0 | 1.2 | 0.5 | 1.8 | 18 | 390 | 330 | 500 |
16 | 2.0 | 1.2 | 0.5 | 1.8 | 19 | 460 | 360 | 500 |
25 | 2.0 | 1.2 | 0.5 | 1.8 | 20 | 580 | 420 | 500 |
35 | 2.0 | 1.2 | 0.5 | 1.8 | 21 | 700 | 480 | 500 |
50 | 2.0 | 1.2 | 0.5 | 1.8 | 23 | 840 | 550 | 500 |
70 | 2.0 | 1.2 | 0.5 | 1.8 | 24 | 1,080 | 650 | 500 |
95 | 2.0 | 1.2 | 0.5 | 1.8 | 26 | 1,360 | 770 | 500 |
120 | 2.0 | 1.2 | 0.5 | 1.8 | 28 | 1,620 | 880 | 500 |
150 | 2.0 | 1.2 | 0.5 | 1.8 | 29 | 1,920 | 990 | 500 |
185 | 2.0 | 1.2 | 0.5 | 1.9 | 31 | 2,300 | 1,150 | 500 |
240 | 2.0 | 1.2 | 0.5 | 1.9 | 33 | 2,890 | 1,380 | 500 |
300 | 2.0 | 1.2 | 0.5 | 2.0 | 36 | 3,510 | 1,610 | 500 |
400 | 2.0 | 1.2 | 0.5 | 2.1 | 37 | 4,380 | 1,950 | 500 |
d | ||||||||
630 | 2.4 | 1.3 | 0.5 | 2.4 | 47 | 7,000 | 2,970 | 500 |
Three-core,CU/XLPE/STA/PVC or AL/XLPE/STA/PVC (Table 18)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.0 | 1.2 | 0.5 | 1.8 | 28 | 910 | 720 | 500 |
16 | 2.0 | 1.2 | 0.5 | 1.9 | 29 | 1,120 | 820 | 500 |
25 | 2.0 | 1.2 | 0.5 | 1.9 | 32 | 1,480 | 1,000 | 500 |
35 | 2.0 | 1.2 | 0.5 | 2.0 | 35 | 1,840 | 1,170 | 500 |
50 | 2.0 | 1.2 | 0.5 | 2.1 | 38 | 1,300 | 1,410 | 500 |
70 | 2.0 | 1.2 | 0.5 | 2.2 | 43 | 3,390 | 2,100 | 500 |
95 | 2.0 | 1.2 | 0.5 | 2.3 | 46 | 4,330 | 2,530 | 500 |
120 | 2.0 | 1.3 | 0.5 | 2.4 | 50 | 5,180 | 2,910 | 500 |
150 | 2.0 | 1.4 | 0.5 | 2.6 | 54 | 6,180 | 3,370 | 500 |
185 | 2.0 | 1.4 | 0.5 | 2.7 | 57 | 7,120 | 3,920 | 500 |
240 | 2.0 | 1.5 | 0.5 | 2.8 | 63 | 9,350 | 4,750 | 400 |
300 | 2.0 | 1.6 | 0.5 | 3.0 | 68 | 11,340 | 5,550 | 300 |
400 | 2.0 | 1.8 | 0.5 | 3.3 | 76 | 14,220 | 6,830 | 300 |
500 | 2.2 | 1.9 | 0.5 | 3.5 | 84 | 17,850 | 8,380 | 250 |
3.6/6(7.2)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable
Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 19)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.8 | 15 | 320 | 260 | 500 |
16 | 2.5 | 1.8 | 18 | 390 | 290 | 500 |
25 | 2.5 | 1.8 | 20 | 500 | 340 | 500 |
35 | 2.5 | 1.8 | 21 | 610 | 400 | 500 |
50 | 2.5 | 1.8 | 22 | 750 | 450 | 500 |
70 | 2.5 | 1.8 | 24 | 970 | 550 | 500 |
95 | 2.5 | 1.8 | 25 | 1,250 | 660 | 500 |
120 | 2.5 | 1.8 | 27 | 1,500 | 760 | 500 |
150 | 2.5 | 1.8 | 28 | 1,790 | 860 | 500 |
185 | 2.5 | 1.9 | 30 | 2,150 | 1,000 | 500 |
240 | 2.6 | 1.9 | 33 | 2,770 | 1,250 | 500 |
300 | 2.8 | 2.0 | 35 | 3,400 | 1,500 | 500 |
400 | 3.0 | 2.1 | 39 | 4,280 | 1.850 | 500 |
500 | 3.2 | 2.2 | 43 | 5,400 | 2,280 | 500 |
630 | 3.2 | 2.4 | 47 | 6,830 | 2,800 | 500 |
800 | 3.2 | 2.5 | 51 | 8,570 | 3,400 | 400 |
1,000 | 3.2 | 2.6 | 56 | 10,590 | 4,110 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 20)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.9 | 33 | 980 | 790 | 500 |
16 | 2.5 | 2.0 | 35 | 1,190 | 890 | 500 |
25 | 2.5 | 2.1 | 38 | 1,560 | 1,080 | 500 |
35 | 2.5 | 2.2 | 40 | 1,930 | 1,270 | 500 |
50 | 2.5 | 2.3 | 43 | 2,370 | 1,480 | 500 |
70 | 2.5 | 2.4 | 47 | 3,110 | 1,820 | 500 |
95 | 2.5 | 2.5 | 51 | 4,000 | 2,200 | 500 |
120 | 2.5 | 2.6 | 54 | 4,820 | 2,550 | 500 |
150 | 2.5 | 2.7 | 58 | 5,770 | 2,970 | 500 |
185 | 2.5 | 2.8 | 61 | 6,960 | 3,460 | 500 |
240 | 2.6 | 3.0 | 68 | 8,940 | 4,340 | 400 |
300 | 2.8 | 3.2 | 73 | 10,980 | 5,190 | 300 |
400 | 3.0 | 3.5 | 81 | 13,820 | 6,440 | 250 |
500 | 3.2 | 3.7 | 90 | 17,390 | 7,910 | 200 |
3.6/6(7.2)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC orAL/XLPE/AWA/PVC (Table 21)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 0.9 | 1.8 | 22 | 610 | 550 | 500 |
16 | 2.5 | 1.2 | 1.6 | 1.8 | 24 | 680 | 580 | 500 |
25 | 2.5 | 1.2 | 1.6 | 1.8 | 25 | 810 | 660 | 500 |
35 | 2.5 | 1.2 | 1.6 | 1.8 | 26 | 940 | 730 | 500 |
50 | 2.5 | 1.2 | 1.6 | 1.8 | 27 | 1,100 | 810 | 500 |
70 | 2.5 | 1.2 | 1.6 | 1.8 | 29 | 1,350 | 930 | 500 |
95 | 2.5 | 1.2 | 1.6 | 1.9 | 31 | 1,670 | 1,080 | 500 |
120 | 2.5 | 1.2 | 1.6 | 1.9 | 32 | 1,950 | 1,200 | 500 |
150 | 2.5 | 1.2 | 1.6 | 2.0 | 34 | 2,270 | 1,350 | 500 |
185 | 2.5 | 1.2 | 2.0 | 2.1 | 37 | 2,770 | 1,620 | 500 |
240 | 2.6 | 1.2 | 2.0 | 2.2 | 40 | 3,440 | 1,930 | 500 |
300 | 2.8 | 1.2 | 2.0 | 2.2 | 42 | 4,120 | 2,210 | 500 |
400 | 3.0 | 1.3 | 2.5 | 2.4 | 47 | 5,250 | 2,820 | 500 |
500 | 3.2 | 1.3 | 2.5 | 2.5 | 51 | 6,450 | 3,340 | 500 |
630 | 3.2 | 1.4 | 2.5 | 2.6 | 55 | 7,990 | 3,950 | 400 |
Three-core,CU/XLPE/SWA/PVC or AL/XLPE/SWA/PVC (Table 22)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 2.0 | 2.1 | 40 | 2,310 | 2,120 | 500 |
16 | 2.5 | 1.2 | 2.0 | 2.2 | 42 | 2,600 | 2,290 | 500 |
25 | 2.5 | 1.2 | 2.0 | 2.3 | 45 | 3,080 | 2,600 | 500 |
35 | 2.5 | 1.3 | 2.5 | 2.4 | 48 | 3,950 | 3,280 | 500 |
50 | 2.5 | 1.3 | 2.5 | 2.5 | 54 | 4,530 | 3,630 | 500 |
70 | 2.5 | 1.4 | 2.5 | 2.6 | 55 | 5,510 | 4,210 | 500 |
95 | 2.5 | 1.5 | 2.5 | 2.8 | 59 | 6,660 | 4,860 | 500 |
120 | 2.5 | 1.5 | 2.5 | 2.9 | 63 | 7,630 | 5,360 | 400 |
150 | 2.5 | 1.6 | 2.5 | 3.0 | 66 | 8,800 | 6,000 | 400 |
185 | 2.5 | 1.7 | 3.15 | 3.2 | 72 | 11,500 | 6,670 | 300 |
240 | 2.6 | 1.8 | 3.15 | 3.4 | 78 | 13,480 | 8,870 | 250 |
300 | 2.8 | 1.9 | 3.15 | 3.6 | 84 | 15,920 | 10,130 | 200 |
400 | 3.0 | 2.0 | 4.0 | 3.9 | 94 | 21,300 | 12,590 | 200 |
500 | 3.2 | 2.1 | 4.0 | 4.1 | 103 | 25,090 | 15,610 | 200 |
3.6/6(7.2)kV,XLPE Insulated Tape Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/ATA/PVCor AL/XLPE/ATA/PVC (Table 23)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 0.5 | 1.8 | 22 | 530 | 460 | 500 |
16 | 2.5 | 1.2 | 0.5 | 1.8 | 23 | 600 | 500 | 500 |
25 | 2.5 | 1.2 | 0.5 | 1.8 | 24 | 730 | 570 | 500 |
35 | 2.5 | 1.2 | 0.5 | 1.8 | 25 | 850 | 630 | 500 |
50 | 2.5 | 1.2 | 0.5 | 1.8 | 26 | 1,000 | 700 | 500 |
70 | 2.5 | 1.2 | 0.5 | 1.8 | 28 | 1,240 | 820 | 500 |
95 | 2.5 | 1.2 | 0.5 | 1.8 | 30 | 1,540 | 950 | 500 |
120 | 2.5 | 1.2 | 0.5 | 1.8 | 31 | 1,820 | 1,080 | 500 |
150 | 2.5 | 1.2 | 0.5 | 1.9 | 33 | 2,120 | 1,200 | 500 |
185 | 2.5 | 1.2 | 0.5 | 1.9 | 35 | 2,520 | 1,370 | 500 |
240 | 2.6 | 1.2 | 0.5 | 2.0 | 37 | 3,180 | 1,670 | 500 |
300 | 2.8 | 1.2 | 0.5 | 2.1 | 40 | 3,850 | 1,950 | 500 |
400 | 3.0 | 1.3 | 0.5 | 2.3 | 44 | 4,800 | 2,370 | 500 |
500 | 3.2 | 1.3 | 0.5 | 2.4 | 48 | 5,960 | 2,840 | 500 |
630 | 3.2 | 1.4 | 0.5 | 2.5 | 52 | 7,450 | 3,410 | 600 |
Three-core,CU/XLPE/STA/PVCor AL/XLPE/STA/PVC (Table 24)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 0.2 | 2.0 | 37 | 1,330 | 1,140 | 500 |
16 | 2.5 | 1.2 | 0.5 | 2.1 | 40 | 1,580 | 1,580 | 500 |
25 | 2.5 | 1.2 | 0.5 | 2.2 | 42 | 2,310 | 1,880 | 500 |
35 | 2.5 | 1.3 | 0.5 | 2.3 | 45 | 2,760 | 2,090 | 500 |
50 | 2.5 | 1.3 | 0.5 | 2.4 | 48 | 3,260 | 2,360 | 500 |
70 | 2.5 | 1.4 | 0.5 | 2.5 | 52 | 4,100 | 2,810 | 500 |
95 | 2.5 | 1.5 | 0.5 | 2.7 | 56 | 5,110 | 3,310 | 500 |
120 | 2.5 | 1.5 | 0.5 | 2.8 | 60 | 5,010 | 3,750 | 400 |
150 | 2.5 | 1.6 | 0.5 | 2.9 | 63 | 7,050 | 4,250 | 400 |
185 | 2.5 | 1.7 | 0.5 | 3.0 | 67 | 9,320 | 4,820 | 400 |
240 | 2.6 | 1.8 | 0.5 | 3.2 | 73 | 10,530 | 5,920 | 300 |
300 | 2.8 | 1.9 | 0.5 | 3.4 | 79 | 12,730 | 6,940 | 300 |
400 | 3.0 | 2.0 | 0.8 | 3.7 | 89 | 16,620 | 9,240 | 200 |
500 | 3.2 | 2.1 | 0.8 | 4.0 | 98 | 20,550 | 11,070 | 200 |
6~30kV XLPE Insulated Power Cables
This product uses the Finland Nextrom(NOKIA)three layer co-extrusion production line for manufacturing chemical cross-linking.
It is suitable for fixed laying of Medium voltage line.
The performance of cables accords with the stipulate of IEC 60502.
Specification of Products
Model | Name | |
CU/XLPE/PVC | AL/XLPE/PVC | Copper or Aluminum Conductor XLPE Insulated and PVC Sheathed Power Cable |
CU/XLPE/PE | AL/XLPE/PE | Copper or Aluminum Conductor XLPE Insulated and PE Sheathed Power Cable |
CU/XLPE/STA/PVC | AL/XLPE/STA/PVC | Copper or Aluminum Conductor XLPE Insulated Steel Tape Armored PVC Sheathed Power Cable |
CU/XLPE/STA/PE | AL/XLPE/STA/PE | Copper or Aluminum Conductor XLPE Insulated Steel Tape Armored PE Sheathed Power Cable |
CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | Copper or Aluminum Conductor XLPE Insulated Steel Wire Armored PVC Sheathed Power Cable |
CU/XLPE/SWA/PE | AL/XLPE/SWA/PE | Copper or Aluminum Conductor XLPE Insulated Steel Wire rmored PE Sheathed Power Cable |
CU/XLPE/CWL/PE | AL/XLPE/CWL/PE | Copper or Aluminum Conductor XLPE Insulated Comprehensive Waterproof Layer Power Cable |
Range of Application
Model | Range of Application | |
CU/XLPE/PVC | AL/XLPE/PVC | It is suitable for laying indoors and outdoors,must be fixed on a bracket in a tunnel, and can be worn through a concrete pipe or laid in a cable ditch and buried directly in loose soil. The cable cannot withstand the pressure,but allows for a certain amount of radiation traction. |
CU/XLPE/PE | AL/XLPE/PE | |
CU/XLPE/STA/PVC | AL/XLPE/STA/PVC | Buried in the ground, the cable can withstand some pressure, but can not withstand large tensile force. |
CU/XLPE/STA/PE | AL/XLPE/STA/PE | |
CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | |
CU/XLPE/SWA/PE | AL/XLPE/SWA/PE | |
CU/XLPE/CWL/PE | AL/XLPE/CWL/PE | It is used for the water resisting requirement of the outer layer of cables |
East Energy
Electrical Engineering
6/6kV,6/10(12)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 25)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.8 | 20 | 450 | 350 | 500 |
25 | 3.4 | 1.8 | 21 | 560 | 400 | 500 |
35 | 3.4 | 1.8 | 22 | 680 | 460 | 500 |
50 | 3.4 | 1.8 | 24 | 810 | 520 | 500 |
70 | 3.4 | 1.8 | 25 | 1,050 | 620 | 500 |
95 | 3.4 | 1.8 | 27 | 1,320 | 730 | 500 |
120 | 3.4 | 1.8 | 28 | 1,580 | 840 | 500 |
150 | 3.4 | 1.9 | 30 | 1,880 | 960 | 500 |
185 | 3.4 | 1.9 | 32 | 2,250 | 1,100 | 500 |
240 | 3.4 | 2.0 | 34 | 2,870 | 1,350 | 500 |
300 | 3.4 | 2.1 | 37 | 3,490 | 1,580 | 500 |
400 | 3.4 | 2.2 | 40 | 4,350 | 1,920 | 500 |
500 | 3.4 | 2.3 | 44 | 5,440 | 2,320 | 500 |
630 | 3.4 | 2.4 | 48 | 6,860 | 2,830 | 500 |
800 | 3.4 | 2.5 | 52 | 8,600 | 3,430 | 400 |
1.000 | 3.4 | 2.6 | 56 | 10,630 | 4,150 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 26)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx.Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
16 | 3.4 | 2.1 | 39 | 1,410 | 1,110 | 500 |
25 | 3.4 | 2.2 | 42 | 1,800 | 1,320 | 500 |
35 | 3.4 | 2.3 | 45 | 2,170 | 1,500 | 500 |
50 | 3.4 | 2.4 | 47 | 2,630 | 1,730 | 500 |
70 | 3.4 | 2.5 | 51 | 3,400 | 2,110 | 500 |
95 | 3.4 | 2.6 | 55 | 4,310 | 2,510 | 500 |
120 | 3.4 | 2.7 | 58 | 5,150 | 2,860 | 500 |
150 | 3.4 | 2.9 | 62 | 6,100 | 3,300 | 500 |
185 | 3.4 | 3.0 | 66 | 7,310 | 3,810 | 500 |
240 | 3.4 | 3.1 | 71 | 9,290 | 4,680 | 400 |
300 | 3.4 | 3.3 | 76 | 11,240 | 5,450 | 300 |
400 | 3.4 | 3.5 | 83 | 14,040 | 6,660 | 250 |
500 | 3.4 | 3.7 | 91 | 17,530 | 8,050 | 200 |
6/6kV,6/10(12)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC or AL/XLPE/AWA/PVC (Table 27)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.2 | 1.6 | 1.8 | 26 | 770 | 670 | 500 |
25 | 3.4 | 1.2 | 1.6 | 1.8 | 27 | 910 | 750 | 500 |
35 | 3.4 | 1.2 | 1.6 | 1.8 | 28 | 1,040 | 820 | 500 |
50 | 3.4 | 1.2 | 1.6 | 1.8 | 29 | 1,190 | 900 | 500 |
70 | 3.4 | 1.2 | 1.6 | 1.9 | 31 | 1,470 | 1,040 | 500 |
95 | 3.4 | 1.2 | 1.6 | 2.0 | 33 | 1,780 | 1,190 | 500 |
120 | 3.4 | 1.2 | 2.0 | 2.0 | 35 | 2,150 | 1,410 | 500 |
150 | 3.4 | 1.2 | 2.0 | 2.1 | 37 | 2,480 | 1,560 | 500 |
185 | 3.4 | 1.2 | 2.0 | 2.1 | 39 | 2,890 | 1,730 | 500 |
240 | 3.4 | 1.2 | 2.0 | 2.2 | 41 | 3,570 | 2,050 | 500 |
300 | 3.4 | 1.2 | 2.0 | 2.3 | 44 | 4,230 | 2,330 | 500 |
400 | 3.4 | 1.3 | 2.5 | 2.4 | 48 | 5,320 | 2,890 | 500 |
500 | 3.4 | 1.3 | 2.5 | 2.5 | 52 | 6,500 | 3,380 | 500 |
630 | 3.4 | 1.4 | 2.5 | 2.6 | 56 | 8,020 | 3,990 | 400 |
Three-core,CU/XLPE/SWA/PVC or AL/XLPE/SWA/PVC (Table 28)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.3 | 2.5 | 2.4 | 47 | 3,700 | 2,700 | 500 |
25 | 3.4 | 1.3 | 2.5 | 2.5 | 50 | 3,900 | 3,430 | 500 |
35 | 3.4 | 1.3 | 2.5 | 2.6 | 53 | 4,430 | 3,770 | 500 |
50 | 3.4 | 1.4 | 2.5 | 2.7 | 56 | 5,080 | 4,190 | 500 |
70 | 3.4 | 1.5 | 2.5 | 2.8 | 60 | 6,050 | 4,750 | 500 |
95 | 3.4 | 1.5 | 2.5 | 2.9 | 64 | 7,180 | 5,380 | 500 |
120 | 3.4 | 1.6 | 2.5 | 3.0 | 67 | 8,230 | 5,960 | 400 |
150 | 3.4 | 1.7 | 3.15 | 3.2 | 72 | 10,100 | 6,580 | 300 |
185 | 3.4 | 1.7 | 3.15 | 3.3 | 76 | 11,610 | 8,110 | 300 |
240 | 3.4 | 1.8 | 3.15 | 3.5 | 82 | 14,110 | 9,510 | 250 |
300 | 3.4 | 1.9 | 3.15 | 3.7 | 87 | 16,420 | 10,630 | 200 |
400 | 3.4 | 2.0 | 4.0 | 4.0 | 96 | 21,700 | 12,880 | 200 |
500 | 3.4 | 2.2 | 4.0 | 4.2 | 104 | 25,280 | 15,800 | 200 |
6/6kV,6/10(12)kV,XLPE Insulated Tape Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/ATA/PVC or AL/XLPE/ATA/PVC (Table 29)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.2 | 0.5 | 1.8 | 25 | 680 | 580 | 500 |
25 | 3.4 | 1.2 | 0.5 | 1.8 | 26 | 810 | 650 | 500 |
35 | 3.4 | 1.2 | 0.5 | 1.8 | 27 | 940 | 720 | 500 |
50 | 3.4 | 1.2 | 0.5 | 1.8 | 28 | 1,090 | 790 | 500 |
70 | 3.4 | 1.2 | 0.5 | 1.9 | 30 | 1,350 | 920 | 500 |
95 | 3.4 | 1.2 | 0.5 | 1.9 | 32 | 1,650 | 1,060 | 500 |
120 | 3.4 | 1.2 | 0.5 | 2.0 | 33 | 1,940 | 1,190 | 500 |
150 | 3.4 | 1.2 | 0.5 | 2.0 | 35 | 2,240 | 1,320 | 500 |
185 | 3.4 | 1.2 | 0.5 | 2.1 | 37 | 2,650 | 1,500 | 500 |
240 | 3.4 | 1.2 | 0.5 | 2.1 | 39 | 3,290 | 1,770 | 500 |
300 | 3.4 | 1.2 | 0.5 | 2.2 | 41 | 3,940 | 2,030 | 500 |
400 | 3.4 | 1.3 | 0.5 | 2.3 | 45 | 4,860 | 2,430 | 500 |
500 | 3.4 | 1.3 | 0.5 | 2.4 | 49 | 5,990 | 2,880 | 500 |
630 | 3.4 | 1.4 | 0.5 | 2.5 | 52 | 7,480 | 3,450 | 500 |
Three-core,CU/XLPE/STA/PVC or AL/XLPE/STA/PVC (Table 30)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.3 | 0.2 | 2.3 | 44 | 2,220 | 1,900 | 500 |
25 | 3.4 | 1.3 | 0.5 | 2.4 | 47 | 2,660 | 2,180 | 500 |
35 | 3.4 | 1.3 | 0.5 | 2.5 | 50 | 3,110 | 2,440 | 500 |
50 | 3.4 | 1.4 | 0.5 | 2.6 | 53 | 3,650 | 2,750 | 500 |
70 | 3.4 | 1.5 | 0.5 | 2.7 | 56 | 4,510 | 3,220 | 500 |
95 | 3.4 | 1.5 | 0.5 | 2.8 | 60 | 5,510 | 3,710 | 500 |
120 | 3.4 | 1.6 | 0.5 | 2.9 | 64 | 6,450 | 4,180 | 500 |
150 | 3.4 | 1.7 | 0.5 | 3.1 | 68 | 7,500 | 4,700 | 400 |
185 | 3.4 | 1.7 | 0.5 | 3.2 | 71 | 8,830 | 5,330 | 400 |
240 | 3.4 | 1.8 | 0.5 | 3.3 | 77 | 10,960 | 6,360 | 300 |
300 | 3.4 | 1.9 | 0.5 | 3.5 | 82 | 13,090 | 7,300 | 250 |
400 | 3.4 | 2.0 | 0.8 | 3.8 | 91 | 16,910 | 9,530 | 200 |
500 | 3.4 | 2.2 | 0.8 | 4.0 | 99 | 20,720 | 11,250 | 200 |
8.7/10kV,8.7/15(17.5)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable
Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 31)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.8 | 24 | 640 | 480 | 500 |
35 | 4.5 | 1.8 | 25 | 760 | 540 | 500 |
50 | 4.5 | 1.8 | 26 | 900 | 610 | 500 |
70 | 4.5 | 1.8 | 28 | 1,140 | 710 | 500 |
95 | 4.5 | 1.8 | 29 | 1,420 | 830 | 500 |
120 | 4.5 | 1.9 | 31 | 1,700 | 950 | 500 |
150 | 4.5 | 1.9 | 32 | 1,990 | 1,070 | 500 |
185 | 4.5 | 2.0 | 34 | 2,380 | 1,230 | 500 |
240 | 4.5 | 2.1 | 37 | 3,010 | 1,490 | 500 |
300 | 4.5 | 2.1 | 39 | 3,620 | 1,720 | 500 |
400 | 4.5 | 2.2 | 42 | 4,490 | 2,070 | 500 |
500 | 4.5 | 2.3 | 46 | 5,600 | 2,480 | 500 |
630 | 4.5 | 2.5 | 50 | 7,050 | 3,010 | 500 |
800 | 4.5 | 2.6 | 54 | 8,800 | 3,630 | 400 |
1,000 | 4.5 | 2.7 | 58 | 10,850 | 4,370 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 32)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
25 | 4.5 | 2.4 | 47 | 2,100 | 1,620 | 500 |
35 | 4.5 | 2.5 | 50 | 2,510 | 1,840 | 500 |
50 | 4.5 | 2.6 | 52 | 2,980 | 2,080 | 500 |
70 | 4.5 | 2.7 | 56 | 3,760 | 2,470 | 500 |
95 | 4.5 | 2.8 | 60 | 4,700 | 2,900 | 500 |
120 | 4.5 | 2.9 | 63 | 5,590 | 3,320 | 500 |
150 | 4.5 | 3.0 | 67 | 6,560 | 3,760 | 500 |
185 | 4.5 | 3.1 | 71 | 7,800 | 4,300 | 400 |
240 | 4.5 | 3.3 | 76 | 9,820 | 5,220 | 300 |
300 | 4.5 | 3.5 | 81 | 11,800 | 6,010 | 300 |
400 | 4.5 | 3.7 | 88 | 14,620 | 7,250 | 250 |
500 | 4.5 | 3.9 | 96 | 18,150 | 8,680 | 200 |
8 .7/10kV,8.7/15(17.5)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC orAL/XLPE/AWA/PVC (Table 33)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.2 | 1.6 | 1.8 | 29 | 1,020 | 860 | 500 |
35 | 4.5 | 1.2 | 1.6 | 1.9 | 30 | 1,170 | 950 | 500 |
50 | 4.5 | 1.2 | 1.6 | 1.9 | 32 | 1,340 | 1,040 | 500 |
70 | 4.5 | 1.2 | 1.6 | 2.0 | 34 | 1,640 | 1,190 | 500 |
95 | 4.5 | 1.2 | 2.0 | 2.1 | 36 | 2,020 | 1,430 | 500 |
120 | 4.5 | 1.2 | 2.0 | 2.1 | 38 | 2,310 | 1,570 | 500 |
150 | 4.5 | 1.2 | 2.0 | 2.2 | 39 | 2,660 | 1,740 | 500 |
185 | 4.5 | 1.2 | 2.0 | 2.2 | 41 | 3,070 | 1,920 | 500 |
240 | 4.5 | 1.2 | 2.0 | 2.3 | 44 | 3,750 | 2,240 | 500 |
300 | 4.5 | 1.3 | 2.5 | 2.4 | 47 | 4,590 | 2,690 | 500 |
400 | 4.5 | 1.3 | 2.5 | 2.5 | 50 | 5,550 | 3,120 | 500 |
500 | 4.5 | 1.4 | 2.5 | 2.6 | 51 | 6,750 | 3,640 | 500 |
630 | 4.5 | 1.4 | 2.5 | 2.7 | 58 | 8,280 | 4,240 | 400 |
Three-core,CU/XLPE/SWA/PVC or AL/XLPE/SWA/PVC (Table 34)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.4 | 2.5 | 2.7 | 55 | 4,560 | 4,080 | 500 |
35 | 4.5 | 1.4 | 2.5 | 2.8 | 58 | 5,080 | 4,410 | 500 |
50 | 4.5 | 1.5 | 2.5 | 2.9 | 61 | 5,740 | 4,840 | 500 |
70 | 4.5 | 1.6 | 2.5 | 3.0 | 65 | 6,770 | 5,480 | 500 |
95 | 4.5 | 1.6 | 2.5 | 3.1 | 69 | 7,890 | 6,100 | 400 |
120 | 4.5 | 1.7 | 3.15 | 3.2 | 74 | 10,900 | 6,700 | 400 |
150 | 4.5 | 1.8 | 3.15 | 3.4 | 77 | 11,030 | 8,220 | 300 |
185 | 4.5 | 1.8 | 3.15 | 3.5 | 81 | 12,490 | 8,980 | 250 |
240 | 4.5 | 1.9 | 4.0 | 3.7 | 89 | 17,500 | 10,440 | 250 |
300 | 4.5 | 2.0 | 4.0 | 3.9 | 94 | 20,100 | 12,130 | 200 |
400 | 4.5 | 2.1 | 4.0 | 4.1 | 101 | 23,600 | 13,970 | 200 |
8.7/10kV,8.7/15(17.5)kV,XLPE Insulated Tape Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/ATA/PVC or AL/XLPE/ATA/PVC (Table 35)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.2 | 0.5 | 1.8 | 28 | 910 | 760 | 500 |
35 | 4.5 | 1.2 | 0.5 | 1.8 | 29 | 1,050 | 830 | 500 |
50 | 4.5 | 1.2 | 0.5 | 1.9 | 30 | 1,210 | 920 | 500 |
70 | 4.5 | 1.2 | 0.5 | 1.9 | 32 | 1,470 | 1,050 | 500 |
95 | 4.5 | 1.2 | 0.5 | 2.0 | 34 | 1,790 | 1,200 | 500 |
120 | 4.5 | 1.2 | 0.5 | 2.0 | 35 | 2,070 | 1,320 | 500 |
150 | 4.5 | 1.2 | 0.5 | 2.1 | 37 | 2,400 | 1,470 | 500 |
185 | 4.5 | 1.2 | 0.5 | 2.1 | 39 | 2,800 | 1,640 | 500 |
240 | 4.5 | 1.2 | 0.5 | 2.2 | 41 | 3,460 | 1,940 | 500 |
300 | 4.5 | 1.3 | 0.5 | 2.3 | 44 | 4,160 | 2,230 | 500 |
400 | 4.5 | 1.3 | 0.5 | 2.4 | 47 | 5,050 | 2,620 | 500 |
500 | 4.5 | 1.4 | 0.5 | 2.5 | 51 | 6,220 | 3,100 | 500 |
630 | 4.5 | 1.4 | 0.5 | 2.6 | 55 | 7,710 | 3,670 | 500 |
Three-core,CU/XLPE/STA/PVC or AL/XLPE/STA/PVC (Table 36)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.4 | 0.5 | 2.6 | 52 | 3,120 | 2,640 | 500 |
35 | 4.5 | 1.4 | 0.5 | 2.6 | 55 | 3,570 | 2,900 | 500 |
50 | 4.5 | 1.5 | 0.5 | 2.7 | 58 | 4,120 | 3,220 | 500 |
70 | 4.5 | 1.6 | 0.5 | 2.9 | 62 | 5,050 | 3,750 | 500 |
95 | 4.5 | 1.6 | 0.5 | 3.0 | 66 | 6,070 | 4,270 | 500 |
120 | 4.5 | 1.7 | 0.5 | 3.1 | 69 | 7,040 | 4,770 | 500 |
150 | 4.5 | 1.8 | 0.5 | 3.2 | 73 | 8,120 | 5,310 | 400 |
185 | 4.5 | 1.8 | 0.5 | 3.3 | 77 | 9,440 | 5,940 | 300 |
240 | 4.5 | 1.9 | 0.5 | 3.5 | 83 | 11,660 | 7,050 | 300 |
300 | 4.5 | 2.0 | 0.8 | 3.7 | 89 | 14,600 | 8,810 | 250 |
400 | 4.5 | 2.1 | 0.8 | 4.0 | 96 | 17,760 | 10,370 | 200 |
500 | 4.5 | 2.3 | 0.8 | 4.2 | 105 | 21,620 | 12,150 | 200 |
12/20(24)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable
Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 37)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
35 | 5.5 | 1.8 | 27 | 840 | 620 | 500 |
50 | 5.5 | 1.8 | 28 | 990 | 690 | 500 |
70 | 5.5 | 1.9 | 30 | 1,230 | 800 | 500 |
95 | 5.5 | 1.9 | 31 | 1,530 | 940 | 500 |
120 | 5.5 | 2.0 | 33 | 1,810 | 1,060 | 500 |
150 | 5.5 | 2.0 | 35 | 2,110 | 1,190 | 500 |
185 | 5.5 | 2.1 | 36 | 2,510 | 1,360 | 500 |
240 | 5.5 | 2.1 | 39 | 3,130 | 1,610 | 500 |
300 | 5.5 | 2.2 | 41 | 3,760 | 1,860 | 500 |
400 | 5.5 | 2.3 | 44 | 4,650 | 2,220 | 500 |
500 | 5.5 | 2.4 | 48 | 5,760 | 2,650 | 500 |
630 | 5.5 | 2.5 | 52 | 7,210 | 3,180 | 500 |
800 | 5.5 | 2.6 | 56 | 8,980 | 3,800 | 400 |
1,000 | 5.5 | 2.8 | 61 | 11,060 | 4,580 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC
(Table 38)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
35 | 5.5 | 2.6 | 54 | 2,850 | 2,080 | 500 |
50 | 5.5 | 2.7 | 57 | 3,340 | 2,450 | 500 |
70 | 5.5 | 2.9 | 61 | 4,150 | 2,850 | 500 |
95 | 5.5 | 3.0 | 65 | 5,110 | 3,310 | 500 |
120 | 5.5 | 3.1 | 68 | 5,990 | 3,730 | 500 |
150 | 5.5 | 3.2 | 72 | 6,980 | 4.180 | 500 |
185 | 5.5 | 3.3 | 75 | 8,240 | 4,740 | 400 |
240 | 5.5 | 3.5 | 81 | 10,310 | 5,700 | 300 |
300 | 5.5 | 3.6 | 86 | 12,350 | 6,570 | 300 |
400 | 5.5 | 3.8 | 93 | 15,220 | 7,830 | 200 |
500 | 5.5 | 4.1 | 101 | 18,800 | 9,320 | 200 |
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
35 | 5.5 | 1.5 | 2.5 | 2.9 | 63 | 5,680 | 5,010 | 500 |
50 | 5.5 | 1.6 | 2.5 | 3.0 | 66 | 6,370 | 5,480 | 500 |
70 | 5.5 | 1.7 | 2.5 | 3.1 | 70 | 7,370 | 6,070 | 400 |
95 | 5.5 | 1.7 | 3.15 | 3.3 | 75 | 9,400 | 7,600 | 300 |
120 | 5.5 | 1.8 | 3.15 | 3.4 | 79 | 10,530 | 8,270 | 300 |
150 | 5.5 | 1.8 | 3.15 | 3.5 | 82 | 11,740 | 8,940 | 300 |
185 | 5.5 | 1.9 | 3.15 | 3.7 | 86 | 13,350 | 9,850 | 250 |
240 | 5.5 | 2.0 | 4.0 | 3.9 | 94 | 18,000 | 11,820 | 200 |
300 | 5.5 | 2.1 | 4.0 | 4.0 | 99 | 20,500 | 13,080 | 200 |
400 | 5.5 | 2.2 | 4.0 | 4.3 | 106 | 23,310 | 15,930 | 200 |
12/20(24)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC orAL/XLPE/AWA/PVC (Table 39)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
35 | 5.5 | 1.2 | 1.6 | 1.9 | 32 | 1,290 | 1,070 | 500 |
50 | 5.5 | 1.2 | 2.0 | 2.0 | 35 | 1,550 | 1,250 | 500 |
70 | 5.5 | 1.2 | 2.0 | 2.1 | 37 | 1,840 | 1,420 | 500 |
95 | 5.5 | 1.2 | 2.0 | 2.1 | 38 | 2,160 | 1,570 | 500 |
120 | 5.5 | 1.2 | 2.0 | 2.2 | 40 | 2,470 | 1,730 | 500 |
150 | 5.5 | 1.2 | 2.0 | 2.2 | 41 | 2,810 | 1,890 | 500 |
185 | 5.5 | 1.2 | 2.0 | 2.3 | 43 | 3,240 | 2,090 | 500 |
240 | 5.5 | 1.3 | 2.5 | 2.4 | 47 | 4,100 | 2,580 | 500 |
300 | 5.5 | 1.3 | 2.5 | 2.5 | 49 | 4,800 | 2,890 | 500 |
400 | 5.5 | 1.4 | 2.5 | 2.6 | 53 | 5,780 | 3,350 | 500 |
500 | 5.5 | 1.4 | 2.5 | 2.7 | 57 | 6,970 | 3,850 | 500 |
630 | 5.5 | 1.5 | 2.5 | 2.8 | 60 | 8,540 | 4,500 | 400 |
Three-core,CU/XLPE/SWA/PVCorAL/XLPE/SWA/PVC (Table 40)
Product composition
Conductor: Made of high-quality copper conductor, it has excellent conductivity, ensuring low resistance and high transmission efficiency.
Insulation layer: Made of cross-linked polyethylene, it has good electrical properties and high temperature resistance, ensuring stability during long-term use.
Sheath material: The cable is made of aluminum corrugated sheath on the outside, which has good mechanical protection and can prevent external physical damage.
Additional protective layer: Some models can choose PVC sheath to provide additional waterproof and chemical corrosion protection.
Why Choose Us?
Strict quality control: We provide full-process quality control from production to delivery to ensure that every product meets the highest standards.
Global business support: We have a wide market network in many countries and regions, and can respond to customer needs in a timely manner and provide fast after-sales service.
FAQs
Q:Is it easy to install?
A: This cable adopts standardized design, simple installation, and is suitable for various power systems. For specific environments, you can choose the appropriate sheath material according to your needs.
Q:What is the service life of this product?
A: Due to the use of high-quality XLPE insulation and aluminum corrugated sheath, our cable products have a service life of more than 20 years and can work stably in high temperature, high humidity and harsh environments.