Select the cable according to the system voltage and grounding method. U₀ is the rated power-frequency voltage between conductor and screen/armour; U is the rated voltage between conductors. The maximum system voltage Um must not exceed the cable’s specified value.
| System Nominal Voltage | Cable Rated Voltage U₀/U | Maximum System Voltage Um |
|---|---|---|
| 6 kV | 3.6/6 kV | 7.2 kV |
| 10 kV | 6/10 kV | 12 kV |
| 15 kV | 8.7/15 kV | 17.5 kV |
| 20 kV | 12/20 kV | 24 kV |
| 30 kV | 18/30 kV | 36 kV |
| 35 kV | 26/35 kV | 42 kV |
For ungrounded or resonant-grounded systems, select a higher U₀ rating. For effectively grounded systems, the standard U₀/U rating is usually sufficient.
Copper: Higher conductivity, better short-circuit performance, suitable for critical circuits and limited installation space.
Aluminium: Lower weight and cost, suitable for long routes where weight and budget are priorities.
Cross-section: Determine by load current, short-circuit current, voltage drop, ambient temperature, soil thermal resistivity, and grouping factor. Typical three-core medium voltage range: 25–400 mm².
XLPE insulation allows a continuous conductor temperature of 90°C and a short-circuit temperature of 250°C for up to 5 seconds. Insulation thickness is specified by IEC 60502-2 according to voltage rating.
Choose galvanised steel wire armour for:
Direct burial without additional conduit
Vertical shafts and steep routes requiring tensile strength
Areas with ground movement, heavy traffic, or rodent risk
Bridge or tunnel spans where mechanical damage is possible
For highly corrosive environments, specify an additional anti-corrosion layer or a PE oversheath.
PVC: General purpose, flame-retardant, cost-effective.
PE: Better moisture resistance, preferred for direct burial and wet locations.
LSZH: Low smoke and halogen-free, for tunnels, indoor substations, and public infrastructure.
Direct burial: Use SWA with PE or PVC oversheath; consider soil thermal resistivity and burial depth.
Ducts and trenches: SWA provides extra protection during pulling and against subsequent damage.
Vertical shafts: Steel wire armour supports cable weight; calculate pulling tension and support spacing.
Tunnels and indoor routes: LSZH oversheath may be required for fire safety.
Bridge or long spans: Verify pulling tension, support spacing, and bending radius.
Minimum bending radius is typically 12–15 times the cable outer diameter for static installation and 20 times during pulling. Select drum length according to route length, number of joints, transport limits, and installation method.
Specify the applicable standard: IEC 60502-2, GB/T 12706.2, BS 6622, VDE 0276-620, or project-specific requirements.
| Parameter | Standard Range / Option |
|---|---|
| Standard | IEC 60502-2, GB/T 12706.2 |
| Rated Voltage U₀/U | 3.6/6 kV, 6/10 kV, 8.7/15 kV, 12/20 kV, 18/30 kV, 26/35 kV |
| Maximum System Voltage Um | 7.2 kV, 12 kV, 17.5 kV, 24 kV, 36 kV, 42 kV |
| Number of Cores | 3 |
| Conductor | Copper or aluminium, Class 1 or 2, 25–400 mm² |
| Insulation | XLPE (cross-linked polyethylene) |
| Insulation Temperature | 90°C continuous; 250°C short-circuit (max. 5 s) |
| Armour | Galvanised steel wire, fine or coarse, optional anti-corrosion layer |
| Oversheath | PVC, PE, or LSZH; black, red, or as specified |
| Operating Temperature | -40°C to +90°C conductor |
| Bending Radius | ≥12 × outer diameter (static); ≥20 × outer diameter (installation) |
| Installation | Direct burial, duct, trench, tunnel, vertical shaft, bridge |
| Packing | Steel or wooden drum; custom drum length available |
Medium voltage three-phase distribution networks
Urban and industrial underground power lines
Direct-buried feeders and branch circuits
Tunnel, shaft, and bridge cable routes
Mine and quarry power supply
Connections between switchgear, transformers, and cable termination boxes
To receive an accurate quotation, please provide:
Rated voltage U₀/U
Conductor material and cross-section
Number of cores: 3
Oversheath material: PVC, PE, or LSZH
Armour type: fine or coarse galvanised steel wire
Required standard: IEC 60502-2, GB/T 12706.2, BS 6622, or other
Total length and preferred drum length
Installation environment and any special requirements
1.8/3(3.6)kV,XLPE Insulated Tape Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/ATA/PVC or AL/XLPE/ATA/PVC (Table 17)
Conductor Nominal Area | Inulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.0 | 1.2 | 0.5 | 1.8 | 18 | 390 | 330 | 500 |
16 | 2.0 | 1.2 | 0.5 | 1.8 | 19 | 460 | 360 | 500 |
25 | 2.0 | 1.2 | 0.5 | 1.8 | 20 | 580 | 420 | 500 |
35 | 2.0 | 1.2 | 0.5 | 1.8 | 21 | 700 | 480 | 500 |
50 | 2.0 | 1.2 | 0.5 | 1.8 | 23 | 840 | 550 | 500 |
70 | 2.0 | 1.2 | 0.5 | 1.8 | 24 | 1,080 | 650 | 500 |
95 | 2.0 | 1.2 | 0.5 | 1.8 | 26 | 1,360 | 770 | 500 |
120 | 2.0 | 1.2 | 0.5 | 1.8 | 28 | 1,620 | 880 | 500 |
150 | 2.0 | 1.2 | 0.5 | 1.8 | 29 | 1,920 | 990 | 500 |
185 | 2.0 | 1.2 | 0.5 | 1.9 | 31 | 2,300 | 1,150 | 500 |
240 | 2.0 | 1.2 | 0.5 | 1.9 | 33 | 2,890 | 1,380 | 500 |
300 | 2.0 | 1.2 | 0.5 | 2.0 | 36 | 3,510 | 1,610 | 500 |
400 | 2.0 | 1.2 | 0.5 | 2.1 | 37 | 4,380 | 1,950 | 500 |
d | ||||||||
630 | 2.4 | 1.3 | 0.5 | 2.4 | 47 | 7,000 | 2,970 | 500 |
Three-core,CU/XLPE/STA/PVC or AL/XLPE/STA/PVC (Table 18)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.0 | 1.2 | 0.5 | 1.8 | 28 | 910 | 720 | 500 |
16 | 2.0 | 1.2 | 0.5 | 1.9 | 29 | 1,120 | 820 | 500 |
25 | 2.0 | 1.2 | 0.5 | 1.9 | 32 | 1,480 | 1,000 | 500 |
35 | 2.0 | 1.2 | 0.5 | 2.0 | 35 | 1,840 | 1,170 | 500 |
50 | 2.0 | 1.2 | 0.5 | 2.1 | 38 | 1,300 | 1,410 | 500 |
70 | 2.0 | 1.2 | 0.5 | 2.2 | 43 | 3,390 | 2,100 | 500 |
95 | 2.0 | 1.2 | 0.5 | 2.3 | 46 | 4,330 | 2,530 | 500 |
120 | 2.0 | 1.3 | 0.5 | 2.4 | 50 | 5,180 | 2,910 | 500 |
150 | 2.0 | 1.4 | 0.5 | 2.6 | 54 | 6,180 | 3,370 | 500 |
185 | 2.0 | 1.4 | 0.5 | 2.7 | 57 | 7,120 | 3,920 | 500 |
240 | 2.0 | 1.5 | 0.5 | 2.8 | 63 | 9,350 | 4,750 | 400 |
300 | 2.0 | 1.6 | 0.5 | 3.0 | 68 | 11,340 | 5,550 | 300 |
400 | 2.0 | 1.8 | 0.5 | 3.3 | 76 | 14,220 | 6,830 | 300 |
500 | 2.2 | 1.9 | 0.5 | 3.5 | 84 | 17,850 | 8,380 | 250 |
3.6/6(7.2)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable
Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 19)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.8 | 15 | 320 | 260 | 500 |
16 | 2.5 | 1.8 | 18 | 390 | 290 | 500 |
25 | 2.5 | 1.8 | 20 | 500 | 340 | 500 |
35 | 2.5 | 1.8 | 21 | 610 | 400 | 500 |
50 | 2.5 | 1.8 | 22 | 750 | 450 | 500 |
70 | 2.5 | 1.8 | 24 | 970 | 550 | 500 |
95 | 2.5 | 1.8 | 25 | 1,250 | 660 | 500 |
120 | 2.5 | 1.8 | 27 | 1,500 | 760 | 500 |
150 | 2.5 | 1.8 | 28 | 1,790 | 860 | 500 |
185 | 2.5 | 1.9 | 30 | 2,150 | 1,000 | 500 |
240 | 2.6 | 1.9 | 33 | 2,770 | 1,250 | 500 |
300 | 2.8 | 2.0 | 35 | 3,400 | 1,500 | 500 |
400 | 3.0 | 2.1 | 39 | 4,280 | 1.850 | 500 |
500 | 3.2 | 2.2 | 43 | 5,400 | 2,280 | 500 |
630 | 3.2 | 2.4 | 47 | 6,830 | 2,800 | 500 |
800 | 3.2 | 2.5 | 51 | 8,570 | 3,400 | 400 |
1,000 | 3.2 | 2.6 | 56 | 10,590 | 4,110 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 20)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.9 | 33 | 980 | 790 | 500 |
16 | 2.5 | 2.0 | 35 | 1,190 | 890 | 500 |
25 | 2.5 | 2.1 | 38 | 1,560 | 1,080 | 500 |
35 | 2.5 | 2.2 | 40 | 1,930 | 1,270 | 500 |
50 | 2.5 | 2.3 | 43 | 2,370 | 1,480 | 500 |
70 | 2.5 | 2.4 | 47 | 3,110 | 1,820 | 500 |
95 | 2.5 | 2.5 | 51 | 4,000 | 2,200 | 500 |
120 | 2.5 | 2.6 | 54 | 4,820 | 2,550 | 500 |
150 | 2.5 | 2.7 | 58 | 5,770 | 2,970 | 500 |
185 | 2.5 | 2.8 | 61 | 6,960 | 3,460 | 500 |
240 | 2.6 | 3.0 | 68 | 8,940 | 4,340 | 400 |
300 | 2.8 | 3.2 | 73 | 10,980 | 5,190 | 300 |
400 | 3.0 | 3.5 | 81 | 13,820 | 6,440 | 250 |
500 | 3.2 | 3.7 | 90 | 17,390 | 7,910 | 200 |
3.6/6(7.2)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC orAL/XLPE/AWA/PVC (Table 21)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 0.9 | 1.8 | 22 | 610 | 550 | 500 |
16 | 2.5 | 1.2 | 1.6 | 1.8 | 24 | 680 | 580 | 500 |
25 | 2.5 | 1.2 | 1.6 | 1.8 | 25 | 810 | 660 | 500 |
35 | 2.5 | 1.2 | 1.6 | 1.8 | 26 | 940 | 730 | 500 |
50 | 2.5 | 1.2 | 1.6 | 1.8 | 27 | 1,100 | 810 | 500 |
70 | 2.5 | 1.2 | 1.6 | 1.8 | 29 | 1,350 | 930 | 500 |
95 | 2.5 | 1.2 | 1.6 | 1.9 | 31 | 1,670 | 1,080 | 500 |
120 | 2.5 | 1.2 | 1.6 | 1.9 | 32 | 1,950 | 1,200 | 500 |
150 | 2.5 | 1.2 | 1.6 | 2.0 | 34 | 2,270 | 1,350 | 500 |
185 | 2.5 | 1.2 | 2.0 | 2.1 | 37 | 2,770 | 1,620 | 500 |
240 | 2.6 | 1.2 | 2.0 | 2.2 | 40 | 3,440 | 1,930 | 500 |
300 | 2.8 | 1.2 | 2.0 | 2.2 | 42 | 4,120 | 2,210 | 500 |
400 | 3.0 | 1.3 | 2.5 | 2.4 | 47 | 5,250 | 2,820 | 500 |
500 | 3.2 | 1.3 | 2.5 | 2.5 | 51 | 6,450 | 3,340 | 500 |
630 | 3.2 | 1.4 | 2.5 | 2.6 | 55 | 7,990 | 3,950 | 400 |
Three-core,CU/XLPE/SWA/PVC or AL/XLPE/SWA/PVC (Table 22)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 2.0 | 2.1 | 40 | 2,310 | 2,120 | 500 |
16 | 2.5 | 1.2 | 2.0 | 2.2 | 42 | 2,600 | 2,290 | 500 |
25 | 2.5 | 1.2 | 2.0 | 2.3 | 45 | 3,080 | 2,600 | 500 |
35 | 2.5 | 1.3 | 2.5 | 2.4 | 48 | 3,950 | 3,280 | 500 |
50 | 2.5 | 1.3 | 2.5 | 2.5 | 54 | 4,530 | 3,630 | 500 |
70 | 2.5 | 1.4 | 2.5 | 2.6 | 55 | 5,510 | 4,210 | 500 |
95 | 2.5 | 1.5 | 2.5 | 2.8 | 59 | 6,660 | 4,860 | 500 |
120 | 2.5 | 1.5 | 2.5 | 2.9 | 63 | 7,630 | 5,360 | 400 |
150 | 2.5 | 1.6 | 2.5 | 3.0 | 66 | 8,800 | 6,000 | 400 |
185 | 2.5 | 1.7 | 3.15 | 3.2 | 72 | 11,500 | 6,670 | 300 |
240 | 2.6 | 1.8 | 3.15 | 3.4 | 78 | 13,480 | 8,870 | 250 |
300 | 2.8 | 1.9 | 3.15 | 3.6 | 84 | 15,920 | 10,130 | 200 |
400 | 3.0 | 2.0 | 4.0 | 3.9 | 94 | 21,300 | 12,590 | 200 |
500 | 3.2 | 2.1 | 4.0 | 4.1 | 103 | 25,090 | 15,610 | 200 |
3.6/6(7.2)kV,XLPE Insulated Tape Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/ATA/PVCor AL/XLPE/ATA/PVC (Table 23)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 0.5 | 1.8 | 22 | 530 | 460 | 500 |
16 | 2.5 | 1.2 | 0.5 | 1.8 | 23 | 600 | 500 | 500 |
25 | 2.5 | 1.2 | 0.5 | 1.8 | 24 | 730 | 570 | 500 |
35 | 2.5 | 1.2 | 0.5 | 1.8 | 25 | 850 | 630 | 500 |
50 | 2.5 | 1.2 | 0.5 | 1.8 | 26 | 1,000 | 700 | 500 |
70 | 2.5 | 1.2 | 0.5 | 1.8 | 28 | 1,240 | 820 | 500 |
95 | 2.5 | 1.2 | 0.5 | 1.8 | 30 | 1,540 | 950 | 500 |
120 | 2.5 | 1.2 | 0.5 | 1.8 | 31 | 1,820 | 1,080 | 500 |
150 | 2.5 | 1.2 | 0.5 | 1.9 | 33 | 2,120 | 1,200 | 500 |
185 | 2.5 | 1.2 | 0.5 | 1.9 | 35 | 2,520 | 1,370 | 500 |
240 | 2.6 | 1.2 | 0.5 | 2.0 | 37 | 3,180 | 1,670 | 500 |
300 | 2.8 | 1.2 | 0.5 | 2.1 | 40 | 3,850 | 1,950 | 500 |
400 | 3.0 | 1.3 | 0.5 | 2.3 | 44 | 4,800 | 2,370 | 500 |
500 | 3.2 | 1.3 | 0.5 | 2.4 | 48 | 5,960 | 2,840 | 500 |
630 | 3.2 | 1.4 | 0.5 | 2.5 | 52 | 7,450 | 3,410 | 600 |
Three-core,CU/XLPE/STA/PVCor AL/XLPE/STA/PVC (Table 24)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
10 | 2.5 | 1.2 | 0.2 | 2.0 | 37 | 1,330 | 1,140 | 500 |
16 | 2.5 | 1.2 | 0.5 | 2.1 | 40 | 1,580 | 1,580 | 500 |
25 | 2.5 | 1.2 | 0.5 | 2.2 | 42 | 2,310 | 1,880 | 500 |
35 | 2.5 | 1.3 | 0.5 | 2.3 | 45 | 2,760 | 2,090 | 500 |
50 | 2.5 | 1.3 | 0.5 | 2.4 | 48 | 3,260 | 2,360 | 500 |
70 | 2.5 | 1.4 | 0.5 | 2.5 | 52 | 4,100 | 2,810 | 500 |
95 | 2.5 | 1.5 | 0.5 | 2.7 | 56 | 5,110 | 3,310 | 500 |
120 | 2.5 | 1.5 | 0.5 | 2.8 | 60 | 5,010 | 3,750 | 400 |
150 | 2.5 | 1.6 | 0.5 | 2.9 | 63 | 7,050 | 4,250 | 400 |
185 | 2.5 | 1.7 | 0.5 | 3.0 | 67 | 9,320 | 4,820 | 400 |
240 | 2.6 | 1.8 | 0.5 | 3.2 | 73 | 10,530 | 5,920 | 300 |
300 | 2.8 | 1.9 | 0.5 | 3.4 | 79 | 12,730 | 6,940 | 300 |
400 | 3.0 | 2.0 | 0.8 | 3.7 | 89 | 16,620 | 9,240 | 200 |
500 | 3.2 | 2.1 | 0.8 | 4.0 | 98 | 20,550 | 11,070 | 200 |
6~30kV XLPE Insulated Power Cables
This product uses the Finland Nextrom(NOKIA)three layer co-extrusion production line for manufacturing chemical cross-linking.
It is suitable for fixed laying of Medium voltage line.
The performance of cables accords with the stipulate of IEC 60502.
Specification of Products
Model | Name | |
CU/XLPE/PVC | AL/XLPE/PVC | Copper or Aluminum Conductor XLPE Insulated and PVC Sheathed Power Cable |
CU/XLPE/PE | AL/XLPE/PE | Copper or Aluminum Conductor XLPE Insulated and PE Sheathed Power Cable |
CU/XLPE/STA/PVC | AL/XLPE/STA/PVC | Copper or Aluminum Conductor XLPE Insulated Steel Tape Armored PVC Sheathed Power Cable |
CU/XLPE/STA/PE | AL/XLPE/STA/PE | Copper or Aluminum Conductor XLPE Insulated Steel Tape Armored PE Sheathed Power Cable |
CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | Copper or Aluminum Conductor XLPE Insulated Steel Wire Armored PVC Sheathed Power Cable |
CU/XLPE/SWA/PE | AL/XLPE/SWA/PE | Copper or Aluminum Conductor XLPE Insulated Steel Wire rmored PE Sheathed Power Cable |
CU/XLPE/CWL/PE | AL/XLPE/CWL/PE | Copper or Aluminum Conductor XLPE Insulated Comprehensive Waterproof Layer Power Cable |
Range of Application
Model | Range of Application | |
CU/XLPE/PVC | AL/XLPE/PVC | It is suitable for laying indoors and outdoors,must be fixed on a bracket in a tunnel, and can be worn through a concrete pipe or laid in a cable ditch and buried directly in loose soil. The cable cannot withstand the pressure,but allows for a certain amount of radiation traction. |
CU/XLPE/PE | AL/XLPE/PE | |
CU/XLPE/STA/PVC | AL/XLPE/STA/PVC | Buried in the ground, the cable can withstand some pressure, but can not withstand large tensile force. |
CU/XLPE/STA/PE | AL/XLPE/STA/PE | |
CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | |
CU/XLPE/SWA/PE | AL/XLPE/SWA/PE | |
CU/XLPE/CWL/PE | AL/XLPE/CWL/PE | It is used for the water resisting requirement of the outer layer of cables |
East Energy
Electrical Engineering
6/6kV,6/10(12)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 25)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.8 | 20 | 450 | 350 | 500 |
25 | 3.4 | 1.8 | 21 | 560 | 400 | 500 |
35 | 3.4 | 1.8 | 22 | 680 | 460 | 500 |
50 | 3.4 | 1.8 | 24 | 810 | 520 | 500 |
70 | 3.4 | 1.8 | 25 | 1,050 | 620 | 500 |
95 | 3.4 | 1.8 | 27 | 1,320 | 730 | 500 |
120 | 3.4 | 1.8 | 28 | 1,580 | 840 | 500 |
150 | 3.4 | 1.9 | 30 | 1,880 | 960 | 500 |
185 | 3.4 | 1.9 | 32 | 2,250 | 1,100 | 500 |
240 | 3.4 | 2.0 | 34 | 2,870 | 1,350 | 500 |
300 | 3.4 | 2.1 | 37 | 3,490 | 1,580 | 500 |
400 | 3.4 | 2.2 | 40 | 4,350 | 1,920 | 500 |
500 | 3.4 | 2.3 | 44 | 5,440 | 2,320 | 500 |
630 | 3.4 | 2.4 | 48 | 6,860 | 2,830 | 500 |
800 | 3.4 | 2.5 | 52 | 8,600 | 3,430 | 400 |
1.000 | 3.4 | 2.6 | 56 | 10,630 | 4,150 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 26)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx.Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
16 | 3.4 | 2.1 | 39 | 1,410 | 1,110 | 500 |
25 | 3.4 | 2.2 | 42 | 1,800 | 1,320 | 500 |
35 | 3.4 | 2.3 | 45 | 2,170 | 1,500 | 500 |
50 | 3.4 | 2.4 | 47 | 2,630 | 1,730 | 500 |
70 | 3.4 | 2.5 | 51 | 3,400 | 2,110 | 500 |
95 | 3.4 | 2.6 | 55 | 4,310 | 2,510 | 500 |
120 | 3.4 | 2.7 | 58 | 5,150 | 2,860 | 500 |
150 | 3.4 | 2.9 | 62 | 6,100 | 3,300 | 500 |
185 | 3.4 | 3.0 | 66 | 7,310 | 3,810 | 500 |
240 | 3.4 | 3.1 | 71 | 9,290 | 4,680 | 400 |
300 | 3.4 | 3.3 | 76 | 11,240 | 5,450 | 300 |
400 | 3.4 | 3.5 | 83 | 14,040 | 6,660 | 250 |
500 | 3.4 | 3.7 | 91 | 17,530 | 8,050 | 200 |
6/6kV,6/10(12)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC or AL/XLPE/AWA/PVC (Table 27)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.2 | 1.6 | 1.8 | 26 | 770 | 670 | 500 |
25 | 3.4 | 1.2 | 1.6 | 1.8 | 27 | 910 | 750 | 500 |
35 | 3.4 | 1.2 | 1.6 | 1.8 | 28 | 1,040 | 820 | 500 |
50 | 3.4 | 1.2 | 1.6 | 1.8 | 29 | 1,190 | 900 | 500 |
70 | 3.4 | 1.2 | 1.6 | 1.9 | 31 | 1,470 | 1,040 | 500 |
95 | 3.4 | 1.2 | 1.6 | 2.0 | 33 | 1,780 | 1,190 | 500 |
120 | 3.4 | 1.2 | 2.0 | 2.0 | 35 | 2,150 | 1,410 | 500 |
150 | 3.4 | 1.2 | 2.0 | 2.1 | 37 | 2,480 | 1,560 | 500 |
185 | 3.4 | 1.2 | 2.0 | 2.1 | 39 | 2,890 | 1,730 | 500 |
240 | 3.4 | 1.2 | 2.0 | 2.2 | 41 | 3,570 | 2,050 | 500 |
300 | 3.4 | 1.2 | 2.0 | 2.3 | 44 | 4,230 | 2,330 | 500 |
400 | 3.4 | 1.3 | 2.5 | 2.4 | 48 | 5,320 | 2,890 | 500 |
500 | 3.4 | 1.3 | 2.5 | 2.5 | 52 | 6,500 | 3,380 | 500 |
630 | 3.4 | 1.4 | 2.5 | 2.6 | 56 | 8,020 | 3,990 | 400 |
Three-core,CU/XLPE/SWA/PVC or AL/XLPE/SWA/PVC (Table 28)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.3 | 2.5 | 2.4 | 47 | 3,700 | 2,700 | 500 |
25 | 3.4 | 1.3 | 2.5 | 2.5 | 50 | 3,900 | 3,430 | 500 |
35 | 3.4 | 1.3 | 2.5 | 2.6 | 53 | 4,430 | 3,770 | 500 |
50 | 3.4 | 1.4 | 2.5 | 2.7 | 56 | 5,080 | 4,190 | 500 |
70 | 3.4 | 1.5 | 2.5 | 2.8 | 60 | 6,050 | 4,750 | 500 |
95 | 3.4 | 1.5 | 2.5 | 2.9 | 64 | 7,180 | 5,380 | 500 |
120 | 3.4 | 1.6 | 2.5 | 3.0 | 67 | 8,230 | 5,960 | 400 |
150 | 3.4 | 1.7 | 3.15 | 3.2 | 72 | 10,100 | 6,580 | 300 |
185 | 3.4 | 1.7 | 3.15 | 3.3 | 76 | 11,610 | 8,110 | 300 |
240 | 3.4 | 1.8 | 3.15 | 3.5 | 82 | 14,110 | 9,510 | 250 |
300 | 3.4 | 1.9 | 3.15 | 3.7 | 87 | 16,420 | 10,630 | 200 |
400 | 3.4 | 2.0 | 4.0 | 4.0 | 96 | 21,700 | 12,880 | 200 |
500 | 3.4 | 2.2 | 4.0 | 4.2 | 104 | 25,280 | 15,800 | 200 |
6/6kV,6/10(12)kV,XLPE Insulated Tape Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/ATA/PVC or AL/XLPE/ATA/PVC (Table 29)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.2 | 0.5 | 1.8 | 25 | 680 | 580 | 500 |
25 | 3.4 | 1.2 | 0.5 | 1.8 | 26 | 810 | 650 | 500 |
35 | 3.4 | 1.2 | 0.5 | 1.8 | 27 | 940 | 720 | 500 |
50 | 3.4 | 1.2 | 0.5 | 1.8 | 28 | 1,090 | 790 | 500 |
70 | 3.4 | 1.2 | 0.5 | 1.9 | 30 | 1,350 | 920 | 500 |
95 | 3.4 | 1.2 | 0.5 | 1.9 | 32 | 1,650 | 1,060 | 500 |
120 | 3.4 | 1.2 | 0.5 | 2.0 | 33 | 1,940 | 1,190 | 500 |
150 | 3.4 | 1.2 | 0.5 | 2.0 | 35 | 2,240 | 1,320 | 500 |
185 | 3.4 | 1.2 | 0.5 | 2.1 | 37 | 2,650 | 1,500 | 500 |
240 | 3.4 | 1.2 | 0.5 | 2.1 | 39 | 3,290 | 1,770 | 500 |
300 | 3.4 | 1.2 | 0.5 | 2.2 | 41 | 3,940 | 2,030 | 500 |
400 | 3.4 | 1.3 | 0.5 | 2.3 | 45 | 4,860 | 2,430 | 500 |
500 | 3.4 | 1.3 | 0.5 | 2.4 | 49 | 5,990 | 2,880 | 500 |
630 | 3.4 | 1.4 | 0.5 | 2.5 | 52 | 7,480 | 3,450 | 500 |
Three-core,CU/XLPE/STA/PVC or AL/XLPE/STA/PVC (Table 30)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
16 | 3.4 | 1.3 | 0.2 | 2.3 | 44 | 2,220 | 1,900 | 500 |
25 | 3.4 | 1.3 | 0.5 | 2.4 | 47 | 2,660 | 2,180 | 500 |
35 | 3.4 | 1.3 | 0.5 | 2.5 | 50 | 3,110 | 2,440 | 500 |
50 | 3.4 | 1.4 | 0.5 | 2.6 | 53 | 3,650 | 2,750 | 500 |
70 | 3.4 | 1.5 | 0.5 | 2.7 | 56 | 4,510 | 3,220 | 500 |
95 | 3.4 | 1.5 | 0.5 | 2.8 | 60 | 5,510 | 3,710 | 500 |
120 | 3.4 | 1.6 | 0.5 | 2.9 | 64 | 6,450 | 4,180 | 500 |
150 | 3.4 | 1.7 | 0.5 | 3.1 | 68 | 7,500 | 4,700 | 400 |
185 | 3.4 | 1.7 | 0.5 | 3.2 | 71 | 8,830 | 5,330 | 400 |
240 | 3.4 | 1.8 | 0.5 | 3.3 | 77 | 10,960 | 6,360 | 300 |
300 | 3.4 | 1.9 | 0.5 | 3.5 | 82 | 13,090 | 7,300 | 250 |
400 | 3.4 | 2.0 | 0.8 | 3.8 | 91 | 16,910 | 9,530 | 200 |
500 | 3.4 | 2.2 | 0.8 | 4.0 | 99 | 20,720 | 11,250 | 200 |
8.7/10kV,8.7/15(17.5)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable
Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 31)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.8 | 24 | 640 | 480 | 500 |
35 | 4.5 | 1.8 | 25 | 760 | 540 | 500 |
50 | 4.5 | 1.8 | 26 | 900 | 610 | 500 |
70 | 4.5 | 1.8 | 28 | 1,140 | 710 | 500 |
95 | 4.5 | 1.8 | 29 | 1,420 | 830 | 500 |
120 | 4.5 | 1.9 | 31 | 1,700 | 950 | 500 |
150 | 4.5 | 1.9 | 32 | 1,990 | 1,070 | 500 |
185 | 4.5 | 2.0 | 34 | 2,380 | 1,230 | 500 |
240 | 4.5 | 2.1 | 37 | 3,010 | 1,490 | 500 |
300 | 4.5 | 2.1 | 39 | 3,620 | 1,720 | 500 |
400 | 4.5 | 2.2 | 42 | 4,490 | 2,070 | 500 |
500 | 4.5 | 2.3 | 46 | 5,600 | 2,480 | 500 |
630 | 4.5 | 2.5 | 50 | 7,050 | 3,010 | 500 |
800 | 4.5 | 2.6 | 54 | 8,800 | 3,630 | 400 |
1,000 | 4.5 | 2.7 | 58 | 10,850 | 4,370 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 32)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
25 | 4.5 | 2.4 | 47 | 2,100 | 1,620 | 500 |
35 | 4.5 | 2.5 | 50 | 2,510 | 1,840 | 500 |
50 | 4.5 | 2.6 | 52 | 2,980 | 2,080 | 500 |
70 | 4.5 | 2.7 | 56 | 3,760 | 2,470 | 500 |
95 | 4.5 | 2.8 | 60 | 4,700 | 2,900 | 500 |
120 | 4.5 | 2.9 | 63 | 5,590 | 3,320 | 500 |
150 | 4.5 | 3.0 | 67 | 6,560 | 3,760 | 500 |
185 | 4.5 | 3.1 | 71 | 7,800 | 4,300 | 400 |
240 | 4.5 | 3.3 | 76 | 9,820 | 5,220 | 300 |
300 | 4.5 | 3.5 | 81 | 11,800 | 6,010 | 300 |
400 | 4.5 | 3.7 | 88 | 14,620 | 7,250 | 250 |
500 | 4.5 | 3.9 | 96 | 18,150 | 8,680 | 200 |
8 .7/10kV,8.7/15(17.5)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC orAL/XLPE/AWA/PVC (Table 33)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.2 | 1.6 | 1.8 | 29 | 1,020 | 860 | 500 |
35 | 4.5 | 1.2 | 1.6 | 1.9 | 30 | 1,170 | 950 | 500 |
50 | 4.5 | 1.2 | 1.6 | 1.9 | 32 | 1,340 | 1,040 | 500 |
70 | 4.5 | 1.2 | 1.6 | 2.0 | 34 | 1,640 | 1,190 | 500 |
95 | 4.5 | 1.2 | 2.0 | 2.1 | 36 | 2,020 | 1,430 | 500 |
120 | 4.5 | 1.2 | 2.0 | 2.1 | 38 | 2,310 | 1,570 | 500 |
150 | 4.5 | 1.2 | 2.0 | 2.2 | 39 | 2,660 | 1,740 | 500 |
185 | 4.5 | 1.2 | 2.0 | 2.2 | 41 | 3,070 | 1,920 | 500 |
240 | 4.5 | 1.2 | 2.0 | 2.3 | 44 | 3,750 | 2,240 | 500 |
300 | 4.5 | 1.3 | 2.5 | 2.4 | 47 | 4,590 | 2,690 | 500 |
400 | 4.5 | 1.3 | 2.5 | 2.5 | 50 | 5,550 | 3,120 | 500 |
500 | 4.5 | 1.4 | 2.5 | 2.6 | 51 | 6,750 | 3,640 | 500 |
630 | 4.5 | 1.4 | 2.5 | 2.7 | 58 | 8,280 | 4,240 | 400 |
Three-core,CU/XLPE/SWA/PVC or AL/XLPE/SWA/PVC (Table 34)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.4 | 2.5 | 2.7 | 55 | 4,560 | 4,080 | 500 |
35 | 4.5 | 1.4 | 2.5 | 2.8 | 58 | 5,080 | 4,410 | 500 |
50 | 4.5 | 1.5 | 2.5 | 2.9 | 61 | 5,740 | 4,840 | 500 |
70 | 4.5 | 1.6 | 2.5 | 3.0 | 65 | 6,770 | 5,480 | 500 |
95 | 4.5 | 1.6 | 2.5 | 3.1 | 69 | 7,890 | 6,100 | 400 |
120 | 4.5 | 1.7 | 3.15 | 3.2 | 74 | 10,900 | 6,700 | 400 |
150 | 4.5 | 1.8 | 3.15 | 3.4 | 77 | 11,030 | 8,220 | 300 |
185 | 4.5 | 1.8 | 3.15 | 3.5 | 81 | 12,490 | 8,980 | 250 |
240 | 4.5 | 1.9 | 4.0 | 3.7 | 89 | 17,500 | 10,440 | 250 |
300 | 4.5 | 2.0 | 4.0 | 3.9 | 94 | 20,100 | 12,130 | 200 |
400 | 4.5 | 2.1 | 4.0 | 4.1 | 101 | 23,600 | 13,970 | 200 |
8.7/10kV,8.7/15(17.5)kV,XLPE Insulated Tape Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/ATA/PVC or AL/XLPE/ATA/PVC (Table 35)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.2 | 0.5 | 1.8 | 28 | 910 | 760 | 500 |
35 | 4.5 | 1.2 | 0.5 | 1.8 | 29 | 1,050 | 830 | 500 |
50 | 4.5 | 1.2 | 0.5 | 1.9 | 30 | 1,210 | 920 | 500 |
70 | 4.5 | 1.2 | 0.5 | 1.9 | 32 | 1,470 | 1,050 | 500 |
95 | 4.5 | 1.2 | 0.5 | 2.0 | 34 | 1,790 | 1,200 | 500 |
120 | 4.5 | 1.2 | 0.5 | 2.0 | 35 | 2,070 | 1,320 | 500 |
150 | 4.5 | 1.2 | 0.5 | 2.1 | 37 | 2,400 | 1,470 | 500 |
185 | 4.5 | 1.2 | 0.5 | 2.1 | 39 | 2,800 | 1,640 | 500 |
240 | 4.5 | 1.2 | 0.5 | 2.2 | 41 | 3,460 | 1,940 | 500 |
300 | 4.5 | 1.3 | 0.5 | 2.3 | 44 | 4,160 | 2,230 | 500 |
400 | 4.5 | 1.3 | 0.5 | 2.4 | 47 | 5,050 | 2,620 | 500 |
500 | 4.5 | 1.4 | 0.5 | 2.5 | 51 | 6,220 | 3,100 | 500 |
630 | 4.5 | 1.4 | 0.5 | 2.6 | 55 | 7,710 | 3,670 | 500 |
Three-core,CU/XLPE/STA/PVC or AL/XLPE/STA/PVC (Table 36)
Conductor Nominal Area | Insulation Thickness | Approx. Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
25 | 4.5 | 1.4 | 0.5 | 2.6 | 52 | 3,120 | 2,640 | 500 |
35 | 4.5 | 1.4 | 0.5 | 2.6 | 55 | 3,570 | 2,900 | 500 |
50 | 4.5 | 1.5 | 0.5 | 2.7 | 58 | 4,120 | 3,220 | 500 |
70 | 4.5 | 1.6 | 0.5 | 2.9 | 62 | 5,050 | 3,750 | 500 |
95 | 4.5 | 1.6 | 0.5 | 3.0 | 66 | 6,070 | 4,270 | 500 |
120 | 4.5 | 1.7 | 0.5 | 3.1 | 69 | 7,040 | 4,770 | 500 |
150 | 4.5 | 1.8 | 0.5 | 3.2 | 73 | 8,120 | 5,310 | 400 |
185 | 4.5 | 1.8 | 0.5 | 3.3 | 77 | 9,440 | 5,940 | 300 |
240 | 4.5 | 1.9 | 0.5 | 3.5 | 83 | 11,660 | 7,050 | 300 |
300 | 4.5 | 2.0 | 0.8 | 3.7 | 89 | 14,600 | 8,810 | 250 |
400 | 4.5 | 2.1 | 0.8 | 4.0 | 96 | 17,760 | 10,370 | 200 |
500 | 4.5 | 2.3 | 0.8 | 4.2 | 105 | 21,620 | 12,150 | 200 |
12/20(24)kV,XLPE Insulated Unarmored PVC Sheathed Power Cable
Single-core,CU/XLPE/PVC or AL/XLPE/PVC (Table 37)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
35 | 5.5 | 1.8 | 27 | 840 | 620 | 500 |
50 | 5.5 | 1.8 | 28 | 990 | 690 | 500 |
70 | 5.5 | 1.9 | 30 | 1,230 | 800 | 500 |
95 | 5.5 | 1.9 | 31 | 1,530 | 940 | 500 |
120 | 5.5 | 2.0 | 33 | 1,810 | 1,060 | 500 |
150 | 5.5 | 2.0 | 35 | 2,110 | 1,190 | 500 |
185 | 5.5 | 2.1 | 36 | 2,510 | 1,360 | 500 |
240 | 5.5 | 2.1 | 39 | 3,130 | 1,610 | 500 |
300 | 5.5 | 2.2 | 41 | 3,760 | 1,860 | 500 |
400 | 5.5 | 2.3 | 44 | 4,650 | 2,220 | 500 |
500 | 5.5 | 2.4 | 48 | 5,760 | 2,650 | 500 |
630 | 5.5 | 2.5 | 52 | 7,210 | 3,180 | 500 |
800 | 5.5 | 2.6 | 56 | 8,980 | 3,800 | 400 |
1,000 | 5.5 | 2.8 | 61 | 11,060 | 4,580 | 300 |
Three-core,CU/XLPE/PVC or AL/XLPE/PVC
(Table 38)
Conductor Nominal Area | Insulation Thickness | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||
mm² | mm | mm | mm | kg/km | m | |
35 | 5.5 | 2.6 | 54 | 2,850 | 2,080 | 500 |
50 | 5.5 | 2.7 | 57 | 3,340 | 2,450 | 500 |
70 | 5.5 | 2.9 | 61 | 4,150 | 2,850 | 500 |
95 | 5.5 | 3.0 | 65 | 5,110 | 3,310 | 500 |
120 | 5.5 | 3.1 | 68 | 5,990 | 3,730 | 500 |
150 | 5.5 | 3.2 | 72 | 6,980 | 4.180 | 500 |
185 | 5.5 | 3.3 | 75 | 8,240 | 4,740 | 400 |
240 | 5.5 | 3.5 | 81 | 10,310 | 5,700 | 300 |
300 | 5.5 | 3.6 | 86 | 12,350 | 6,570 | 300 |
400 | 5.5 | 3.8 | 93 | 15,220 | 7,830 | 200 |
500 | 5.5 | 4.1 | 101 | 18,800 | 9,320 | 200 |
12/20(24)kV,XLPE Insulated Wire Armored PVC Sheathed Power Cable
Single-core,CU/XLPE/AWA/PVC orAL/XLPE/AWA/PVC (Table 39)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
35 | 5.5 | 1.2 | 1.6 | 1.9 | 32 | 1,290 | 1,070 | 500 |
50 | 5.5 | 1.2 | 2.0 | 2.0 | 35 | 1,550 | 1,250 | 500 |
70 | 5.5 | 1.2 | 2.0 | 2.1 | 37 | 1,840 | 1,420 | 500 |
95 | 5.5 | 1.2 | 2.0 | 2.1 | 38 | 2,160 | 1,570 | 500 |
120 | 5.5 | 1.2 | 2.0 | 2.2 | 40 | 2,470 | 1,730 | 500 |
150 | 5.5 | 1.2 | 2.0 | 2.2 | 41 | 2,810 | 1,890 | 500 |
185 | 5.5 | 1.2 | 2.0 | 2.3 | 43 | 3,240 | 2,090 | 500 |
240 | 5.5 | 1.3 | 2.5 | 2.4 | 47 | 4,100 | 2,580 | 500 |
300 | 5.5 | 1.3 | 2.5 | 2.5 | 49 | 4,800 | 2,890 | 500 |
400 | 5.5 | 1.4 | 2.5 | 2.6 | 53 | 5,780 | 3,350 | 500 |
500 | 5.5 | 1.4 | 2.5 | 2.7 | 57 | 6,970 | 3,850 | 500 |
630 | 5.5 | 1.5 | 2.5 | 2.8 | 60 | 8,540 | 4,500 | 400 |
Three-core,CU/XLPE/SWA/PVCorAL/XLPE/SWA/PVC (Table 40)
Conductor Nominal Area | Insulation Thickness | Approx.Inner Covering Thickness | Armor Wire Size | Outer Sheath Thickness | Approx. Overall Diameter | Approx. Cable Weight | Standard Length Per Drum | |
Copper | Aluminum | |||||||
mm² | mm | mm | mm | mm | mm | kg/km | m | |
35 | 5.5 | 1.5 | 2.5 | 2.9 | 63 | 5,680 | 5,010 | 500 |
50 | 5.5 | 1.6 | 2.5 | 3.0 | 66 | 6,370 | 5,480 | 500 |
70 | 5.5 | 1.7 | 2.5 | 3.1 | 70 | 7,370 | 6,070 | 400 |
95 | 5.5 | 1.7 | 3.15 | 3.3 | 75 | 9,400 | 7,600 | 300 |
120 | 5.5 | 1.8 | 3.15 | 3.4 | 79 | 10,530 | 8,270 | 300 |
150 | 5.5 | 1.8 | 3.15 | 3.5 | 82 | 11,740 | 8,940 | 300 |
185 | 5.5 | 1.9 | 3.15 | 3.7 | 86 | 13,350 | 9,850 | 250 |
240 | 5.5 | 2.0 | 4.0 | 3.9 | 94 | 18,000 | 11,820 | 200 |
300 | 5.5 | 2.1 | 4.0 | 4.0 | 99 | 20,500 | 13,080 | 200 |
400 | 5.5 | 2.2 | 4.0 | 4.3 | 106 | 23,310 | 15,930 | 200 |